29
Safety Light Array
Receiver Wiring
Pin 1
Signal output
Free
Pin 2
24 V DC
24 V DC supply voltage
Pin 3
OSSD1 output
PLC or relay
Pin 4
Acknowledge
Free
Pin 5
Contactor monitor
Free
Pin 6
OSSD2 output
PLC or relay
Pin 7
0 V
0 V supply voltage
Pin 8
Earth/shield
Operational earth
DANGER!
Up to 25 % of the beams, but no more than 20 beams in all, can be blanked in the fix blanking
operating mode.
5.3.0.3 Fix Blanking Procedure
Start
Set the
fix blanking DIP
switch
The number of blanked beams
appears at the display, and the
blanking LED blinks
Press the enter key
on the receiver
Does 00
appear at the display
and does the failure
LED blink?
The Light Array
boots and enables
the outputs
The Safety Light Array
is ready for operation
Anzeige Empfänger
Serial Communication
Cascading
Timing
Restart Inhibit
8
7
6
5
4
3
2
1
ON OFF
Contactor Monitoring
Reduced Resolution
Fix Blanking
S1
Betriebsart Fix Blanking
DIP Switch Settings: Receiver
Position the object
to be suppressed
within the safety field
no
For example,
2 beams are blanked
1. Remove the object from the
safety field
2. Reset the fix blanking DIP switch
3. Switch the light barrier on and off
Display at Receiver
Start with the pilot
beam, move the test
rod through the safety
field
Does the
total number of all
beams appear at the
display?
no