5 Operation
5.2.2 Service mode
The Service mode gives information about:
• Stepping motor position of the individual operating points;
• The most recent fault;
• Flame signal during burner operation.
u
Press [Enter] for approx. 2 sec.
a
The Service mode is activated.
u
Press [Enter] to reach the next information.
No.
Information
0
Stepping motor position in operating point
P0
1
Stepping motor position in operating point
P1
2
Stepping motor position in operating point
P2
3
Stepping motor position in operating point
P3
4
Stepping motor position in operating point
P4
5
Stepping motor position in operating point
P5
6
Stepping motor position in operating point
P6
7
Stepping motor position in operating point
P7
8
Stepping motor position in operating point
P8
9
Stepping motor position in operating point
P9
10
...
18
Most recent fault ... ninth last occurred fault
Display additional information:
1. Detailed error codes / operating status:
u
Press [+].
2. Detailed error codes
u
Press [-] and [+] simultaneously.
Repetition counter:
u
Press [G].
19
Flame signal
Flame quality
Range:
00
...
58
<
50
= poor quality ...
58
= high quality
Recommended value: >
50