6 Commissioning and startup
6.7 Subsequent optimization of the operating points
For safe and economic operation of the plant, the combustion values can subsequently
be corrected.
u
Unplug the bridging plug No. 7 from the combustion manager.
a
The combustion manager drives to stand-by.
u
Briefly press [-] and [+] keys simultaneously.
a
The combustion manager changes to access level.
u
Press [+].
a
The combustion manager changes to setting level.
u
Plug the bridging plug No. 7 on the combustion manager.
a
The burner starts and stops in operating point
P0
(ignition position).
u
Move through the other operating points using the [+] and [-] keys and optimize, if
necessary.
Exit setting level
u
Press [G] and [L/A] simultaneously.
a
The upper operating limit (
bo
) is displayed.
u
Press [G] and [L/A] simultaneously.
a
The lower operating limit is displayed (
bu
).
u
Press [G] and [L/A] simultaneously.
a
The combustion manager changes to operating level.
Installation and Operating Instructions
Gas burner WG20.../1-C ZM-LN (W-FM 25)