6 Commissioning and startup
6.1.1 Connecting measuring devices
Measuring device for the ionization current
u
Remove ionization cable from the plug coupling.
u
Connect the current measuring device in series.
Ionization current
Extraneous light detection from:
1
μ
A
Minimum ionization current:
5
μ
A
Recommended ionization current:
9 ... 15
μ
A
Measuring device for the mixing pressure
u
Open pressure test point for mixing pressure
1
and connect the pressure measuring
device.
Installation and Operating Instructions
Gas burner WG20.../1-C ZM-LN (W-FM 25)
83055116 • 1/2016-05
1