BRUCIATORI DI GAS BISTADIO PROGRESSIVO / MODULANTE

PROGRESSIVE/MODULATING TWO-STAGE GAS BURNERS

ITALIANO

Manuale istruzioni per l'installazione, l'uso 

e la manutenzione

IT

Instruction manual for 

installation, use and maintenance

EN

TBG 80 LX ME /V

 

TBG 110 LX ME /V

 

TBG 140 LX ME /V

 

TBG 200 LX ME /V

 

TBG 260 LX ME /V

TBG 360 LX ME /V

ISTRUZIONI ORIGINALI (IT)

ORIGINAL INSTRUCTIONS (IT)

0006081328_202001

Summary of Contents for TBG 80 LX ME /V

Page 1: ...TALIANO Manuale istruzioni per l installazione l uso e la manutenzione IT Instruction manual for installation use and maintenance EN TBG 80 LX ME V TBG 110 LX ME V TBG 140 LX ME V TBG 200 LX ME V TBG...

Page 2: ......

Page 3: ...rampa gas 12 Collegamenti elettrici 13 Descrizione del funzionamento a modulazione 15 Accensione e regolazione 17 Misurazione della corrente di ionizzazione 18 Sensore fiamma 18 Regolazione aria sulla...

Page 4: ...E GENERALI La data di produzione dell apparecchio mese anno sono indicati sulla targa identificazione bruciatore presente sull apparecchio L apparecchio non adatto a essere usato da persone bambini co...

Page 5: ...cue quelle parti che potrebbero essere potenziali fonti di pericolo AVVERTENZE PER L AVVIAMENTO IL COLLAUDO L USO E LA MANUTENZIONE L avviamento il collaudo e la manutenzione devono essere effet tuati...

Page 6: ...condi zione della categoria di sovratensione III Sguainare l isolante esterno del cavo di alimentazione nella misura strettamente necessaria al collegamento evitando cos che il filo possa venire a co...

Page 7: ...3 Motore ventola 50hz kW 1 1 1 5 2 2 3 5 5 7 5 Motore ventola 60hz kW 1 1 1 5 2 6 3 5 7 5 9 Potenza elettrica assorbita 50hz kW 1 6 2 2 8 3 7 6 5 8 5 Potenza elettrica assorbita 60hz kW 1 6 2 3 2 4 2...

Page 8: ...iquidi 7 Potenza combustibili gassosi 8 Pressione combustibili gassosi 9 Viscosit combustibili liquidi 10 Potenza motore ventilatore 11 Tensione di alimentazione 12 Grado di protezione 13 Paese di cos...

Page 9: ...MIN PROPANO TBG 260 500 kW POTENZA TERMICA MIN PROPANO TBG 360 600 kW IMPORTANTE I campi di lavoro sono ottenuti su caldaie di prova rispondenti alla norma EN676 e sono orientativi per gli accoppiamen...

Page 10: ...Quadro elettrico 8 Motore 9 Servomotore regolazione aria 10 Servomotore regolazione gas 11 Targa identificazione bruciatore 0002471121nom 9 7 8 1 2 3 4 5 6 10 6 1 11 QUADRO ELETTRICO 1 Apparecchiatura...

Page 11: ...0 400 420 590 390 160 235 1350 Modello D E F I L M N TBG 80 LX ME V 175 400 180 178 280 250 325 M12 190 TBG 110 LX ME V 200 450 224 219 320 280 370 M12 235 TBG 140 LX ME V 200 450 240 219 320 280 370...

Page 12: ...o la normativa EN 676 Classe Emissioni NOx in mg kWh gas metano 1 170 2 120 3 80 CARATTERISTICHE TECNICO FUNZIONALI Funzionamento a due stadi progressivi o modulante Possibilit di funzionamento a modu...

Page 13: ...EN 676 e viene fornita separatamente Sono possibili diverse soluzioni di montaggio 1 2 3 della rampa gas Scegliere la posizione pi idonea in base alla conformazione del locale caldaia e alla posizione...

Page 14: ...2 10 9 14 11 13 8 4 7 6 5 3 2 1 0002910950N2 A CURA DELL INSTALLATORE RAMPA GAS FORNITA DAL COSTRUTTORE 1 Valvola di intercettazione manuale 2 Giunto antivibrante 3 Filtro gas 4 Pressostato di minima...

Page 15: ...cciamento alla rete elettrica come previsto dalle normative di sicurezza vigenti Per i collegamenti elettrici linea e termostati vedere il relativo schema elettrico Sguainare l isolante esterno del ca...

Page 16: ...o del bruciatore consentita esclusivamente a personale professionalmente qualificato In caso di reti elettriche a 230 V fase fase se queste sono sbi lanciate la tensione fra elettrodo di rilevazione f...

Page 17: ...ell erogazione aria gas che si portano al punto minimo 200 Se il termostato di caldaia o pressostato di 2 stadio lo consente regolato ad un valore di temperatura o pressione superiore a quella esisten...

Page 18: ...one all indietro e quindi la riduzione dell erogazione aria e gas avviene a brevi intervalli di tempo Con questa manovra il sistema di modulazione cerca di equilibrare la quantit di calore fornito all...

Page 19: ...di rotazione Inserire ora l interruttore generale L apparecchiatura di comando riceve cos tensione ed il programmatore determina l inserzione del bruciatore come descritto nel capitolo Descrizione del...

Page 20: ...co verificare l efficienza dei termostati o pressostati di caldaia l inter vento deve arrestare il bruciatore verificare l efficienza della sonda di temperatura in caldaia l inter vento deve arrestare...

Page 21: ...ciatore lavora alla massima potenza richiesta dall impianto Correggere la posizione del dispositivo chiusura aria della testa di combustione spostandolo in avanti o indietro in modo da avere un flusso...

Page 22: ...MC TBG 260 LX ME TBG 360 LX ME TBG 80 LX P LX PN V TBG 80 LX ME LX MC A A A B B B 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 4 4 4 5 5 5 C A B C TBG 80 LX ME 5 8 TBG 110 LX ME 5 5 TBG 140 LX ME 5 5 TBG 200 LX ME 5...

Page 23: ...imontaggio di centrare esattamente la testa di uscita gas rispetto agli elettrodi per evitare che gli stessi si trovino a mas sa con conseguente bloccaggio del bruciatore Occorrer anche verificare che...

Page 24: ...scritto dopo aver verificato la corretta posizione degli elet trodi di accensione e di ionizzazione CAUTELA AVVERTENZE All atto della chiusura del bruciatore tirare delicatamente verso il quadro elett...

Page 25: ...AGGIO PATTINO E VITI ANNO LEVE TIRANTI SNODI SFERICI CONTROLLO EVENTUALI USURE LUBRIFICAZIONE COMPONENTI ANNO IMPIANTO ELETTRICO VERIFICA CONNESSIONI E SERRAGGIO MORSETTI ANNO INVERTER PULIZIA VENTOLA...

Page 26: ...na o di pagamento sono indipendenti e non fanno riferi mento alla vita attesa di seguito indicata Per condizioni operative normali si intendono applicazioni su caldaie ad acqua e generatori di vapore...

Page 27: ...cazione naturale da batteria di bombole o serbatoio utilizzabile solo per impianti di piccola potenza La capacit di erogazione in fase di gas in funzione delle dimensioni del serba toio e della temper...

Page 28: ...lizzatore Riduttore di 2 salto Uscita 30 hPa mbar Portata il doppio del massimo richiesto dall utilizzatore Filtro a Y Filtro Filtro Presa di pressione Riduttore di 2 salto Uscita 30 hPa mbar Portata...

Page 29: ...ata dall aria caso di prima accensione 3 La pressione del gas insufficiente o eccessiva 4 Passaggio aria tra disco e testa troppo chiuso RIMEDIO 1 Invertire l alimentazione lato 230V del trasformatore...

Page 30: ...SCHEMI ELETTRICI ITALIANO 28 44 0006081328_202001...

Page 31: ...ITALIANO 29 44 0006081328_202001...

Page 32: ...ITALIANO 30 44 0006081328_202001...

Page 33: ...CONTAORE PA PRESSOSTATO ARIA Pm PRESSOSTATO DI MINIMA S1 INTERRUTTORE MARCIAARRESTO S2 PULSANTE SBLOCCO SG INTERRUTTORE GENERALE TA TRASFORMATORE D ACCENSIONE TC TERMOSTATO CALDAIA TS TERMOSTATO DI S...

Page 34: ...SCHEMI ELETTRICI ITALIANO 32 44 0006081328_202001...

Page 35: ...ITALIANO 33 44 0006081328_202001...

Page 36: ...D ITALIANO 34 44 0006081328_202001...

Page 37: ...BT1 BA BP I1 I2 I3 I4 ITALIANO 35 44 0006081328_202001...

Page 38: ...ITALIANO 36 44 0006081328_202001...

Page 39: ...E E ITALIANO 37 44 0006081328_202001...

Page 40: ...ITALIANO 38 44 0006081328_202001...

Page 41: ...ITALIANO 39 44 0006081328_202001...

Page 42: ...ITALIANO 40 44 0006081328_202001...

Page 43: ...ITALIANO 41 44 0006081328_202001...

Page 44: ...ITALIANO 42 44 0006081328_202001...

Page 45: ...POINT REMOTO 0 4 20 mA K7 REL MARCIA INVERTER K16 REL PRESENZA FIAMMA MV MOTORE VENTOLA N1 REGOLATORE ELETTRONICO P1 CONTAORE PA PRESSOSTATO ARIA Pm PRESSOSTATO DI MINIMA PM PRESSOSTATO DI MASSIMA S1...

Page 46: ...ITALIANO 44 44 0006081328_202001...

Page 47: ...ctrical connections 13 Modulation operation description 15 Starting up and regulation 17 Ionisation current measurement 18 Flame sensor 18 Air regulation on the combustion head 19 Ionization probe ele...

Page 48: ...etween 25 C and 55 C The storage time is 3 years GENERAL WARNINGS The equipment production date month year is written on the bur ner identification plate located on the equipment The equipment cannot...

Page 49: ...main switch Cut off the fuel supply using the shut off valve and remove the control wheels from their position Render harmless any potentially dangerous parts WARNINGS FOR START UP TEST USE AND MAINT...

Page 50: ...ove the external insulating seal of the supply pipe necessary for the connection preventing the cable to touch metal parts The use of any electrically fed components entails complying with certain fun...

Page 51: ...ar 75 45 propane emissions mg kWh Class 3 Class 3 50hz fan motor kW 1 1 1 5 2 2 3 5 5 7 5 60hz fan motor kW 1 1 1 5 2 6 3 5 7 5 9 Absorbed electrical power 50hz kW 1 6 2 2 8 3 7 6 5 8 5 Absorbed elect...

Page 52: ...5 Serial number 6 Liquid fuel power 7 Gaseous fuel power 8 Gaseous fuel pressure 9 Liquid fuel viscosity 10 Fan motor power 11 Power supply voltage 12 Protection rating 13 Country of origin and number...

Page 53: ...NT MINIMUM PROPANE THERMAL POWER TBG 260 500 kW MINIMUM PROPANE THERMAL POWER TBG 360 600 kW IMPORTANT The operating ranges are obtained from test boilers corresponding to Standard EN676 and are indic...

Page 54: ...ME 7 Electrical panel 8 Motor 9 Air regulation servomotor 10 Gas regulation servomotor 11 Burner identification plate 0002471121nom 9 7 8 1 2 3 4 5 6 10 6 1 11 ELECTRICAL PANEL 1 Control box 2 Air pre...

Page 55: ...400 420 590 390 160 235 1350 Model D E F I L M N TBG 80 LX ME V 175 400 180 178 280 250 325 M12 190 TBG 110 LX ME V 200 450 224 219 320 280 370 M12 235 TBG 140 LX ME V 200 450 240 219 320 280 370 M12...

Page 56: ...asses defined according to EN 676 standards Class NOx emissions in mg kWh natural gas 1 170 2 120 3 80 TECHNICAL FUNCTIONAL CHARACTERISTICS Operation at two progressive stages modulating Ability to op...

Page 57: ...n is sold separately from the bur ner The gas train can be assembled in different ways 1 2 3 Choose the most rational position for the set up of the boiler room and the position in which the gas pipel...

Page 58: ...11 13 8 4 7 6 5 3 2 1 0002910950N2 TO BE CARRIED OUT BY THE INSTALLER GAS TRAIN SUPPLIED BY THE MANUFACTURER 1 Manual shut off valve 2 Vibration proof joint 3 Gas filter 4 Minimum gas pressure switch...

Page 59: ...gap equal or above 3 mm in accordance with current safety regulations Refer to the wiring diagram for electrical connections line and ther mostats Remove the external insulating seal of the supply pip...

Page 60: ...Only professionally qualified personnel may open the burner electrical switchboard In case of phase phase 230V electrical grids if these latter are unbalanced the voltage between flame detection elec...

Page 61: ...mmer relay moves past the locking position and sends voltage to the air gas supply adjustment servomotors which go to the minimum point 200 If the second stage boiler thermostat or pressure switch all...

Page 62: ...n in gas and air flow take place in short time intervals With this procedure the modulation system attempts to balance the amount of heat supplied to the boiler with respect to the amount the boiler r...

Page 63: ...direction of revolution Now switch on the main switch This powers on the control devi ce and the programmer turns on the burner as described in the chapter Operation description For burner adjustment...

Page 64: ...the thermostats or boiler pressure switches they should shut down the burner when triggered check the efficiency of the temperature probe in the boiler it should shut down the burner when triggered Th...

Page 65: ...pacity required by the system Correct the position of the device that closes the air of the combustion head moving it forward or backward in order to obtain an air flow suitable for the supply with th...

Page 66: ...ME LX MC TBG 260 LX ME TBG 360 LX ME TBG 80 LX P LX PN V TBG 80 LX ME LX MC A A A B B B 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 4 4 4 5 5 5 C A B C TBG 80 LX ME 5 8 TBG 110 LX ME 5 5 TBG 140 LX ME 5 5 TBG 200 L...

Page 67: ...y operations to exactly centre the gas diffuser with respect to the electrodes making sure that they are not earthed which would result in the locking of the burner Verify also that the ignition elect...

Page 68: ...ions described above after having checked the correct position of ignition and ionisation electrodes CAUTION WARNINGS When closing the burner gently pull towards the electrical pa nel putting the two...

Page 69: ...CK OF WEAR AND OPERATION GREASING OF SLIDING BLOCK AND SCREWS YEAR LEVERS TIE RODS BALL JOINTS CHECK OF ANY WEAR COMPONENT LUBRICATION YEAR ELECTRICAL SYSTEM CHECK OF CONNECTIONS AND TERMINAL TIGHTENI...

Page 70: ...contracts and or delivery or payment notes if necessary are independent and do not refer to the expected lifespan stated below Normal operating conditions means applications on water boilers and stea...

Page 71: ...safe operation bb Natural gasification from sets of cylinders or a tank can be used only in low power systems Gas supply capacity on the basis of tank size and minimum outdoor temperature are shown in...

Page 72: ...red by the user 2nd step reducer Output 30 hPa mbar Flow rate double the maximum required by the user Y filter Filter Filter Pressure intake 2nd step reducer Output 30 hPa mbar Flow rate double the ma...

Page 73: ...of first ignition 3 The gas pressure is insufficient or exces sive 4 Air flow between disk and head too nar row REMEDY 1 Invert the ignition transformer power supply 230V side and check using an anal...

Page 74: ...WIRING DIAGRAMS ENGLISH 28 44 0006081328_202001...

Page 75: ...ENGLISH 29 44 0006081328_202001...

Page 76: ...ENGLISH 30 44 0006081328_202001...

Page 77: ...SSURE SWITCH P1 HOUR METER PA AIR PRESSURE SWITCH Pm MINIMUM PRESSURE SWITCH S1 START STOP SWITCH S2 RELEASE BUTTON SG MAIN SWITCH TA IGNITION TRANSFORMER TC BOILER THERMOSTAT TS SAFETY THERMOSTAT X1...

Page 78: ...WIRING DIAGRAMS ENGLISH 32 44 0006081328_202001...

Page 79: ...ENGLISH 33 44 0006081328_202001...

Page 80: ...D ENGLISH 34 44 0006081328_202001...

Page 81: ...BT1 BA BP I1 I2 I3 I4 ENGLISH 35 44 0006081328_202001...

Page 82: ...ENGLISH 36 44 0006081328_202001...

Page 83: ...E E ENGLISH 37 44 0006081328_202001...

Page 84: ...ENGLISH 38 44 0006081328_202001...

Page 85: ...ENGLISH 39 44 0006081328_202001...

Page 86: ...ENGLISH 40 44 0006081328_202001...

Page 87: ...ENGLISH 41 44 0006081328_202001...

Page 88: ...ENGLISH 42 44 0006081328_202001...

Page 89: ...4 20 mA REMOTE SETPOINT K7 INVERTER START RELAY K16 FLAME PRESENCE RELAY MV FAN MOTOR N1 ELECTRONIC REGULATOR P1 HOUR METER PA AIR PRESSURE SWITCH Pm MINIMUM PRESSURE SWITCH PM MAXIMUM PRESSURE SWITC...

Page 90: ...ENGLISH 44 44 0006081328_202001...

Page 91: ......

Page 92: ...Il presente catalogo riveste carattere puramente indicativo La casa pertanto si riserva ogni possibilit di modifica dei dati tecnici e di quant altro in esso riportato Information contained in this c...