10 of 36
• The Heat On symbol is shown on the display when the thermostat is heating.
• Heating for freeze protection is provided whenever the air or floor temperature falls below
40°F (4.5°C), regardless of operating mode.
• The Cool On symbol is shown on the display when the thermostat is cooling.
The thermostat supports two heating system types: 1) conventional, or 2) heat pump.
Conventional Systems
A conventional heating system includes: furnaces, air conditioners, hydronic
heating systems with baseboards, radiant floors, or fan coils and electric heating.
The thermostat supports up to two heating stages, two cooling stages, a fan and
two accessory relays.
Equipment Setting
1H/1C
1H/2C
2H/1C
2H/2C
First stage heating
W1
W1
W1
W1
Second stage heating
-
-
W2
W2
First stage cooling
Y1
Y1
Y1
Y1
Second stage cooling
-
Y2
-
Y2
Fan
G
Accessory 1
Choice of: Humidifier, Dehumidifier, HRV/ERV
Accessory 2
Choice of: Humidifier, Dehumidifier
Heat Pump Systems
A heat pump system may include additional heat sources as backup. The
thermostat supports up to four heating stages, two cooling stages, a reversing
valve, a fan and one accessory relay.
Equipment Setting
1HP
1HP/
1Aux
1HP/
2Aux
2HP
2HP/
1Aux
2HP/
2Aux
First stage heating
Y1
Y1
Y1
Y1
Y1
Y1
Second stage heating
-
W1
W1
Y2
Y2
Y2
Third stage heating
-
-
W2
-
W1
W1
Fourth stage heating
-
-
-
-
-
W2
First stage cooling
Y1
Y1
Y1
Y1
Y1
Y1
Second stage cooling
-
-
-
Y2
Y2
Y2
Fan
G
Accessory 1
Choice of: Humidifier, Dehumidifier, HRV/ERV ventilator
Accessory 2
Reversing valve O relay remains closed during cooling.
Reversing valve B relay remains closed during heating.
Sequence of Operation
Heating and Cooling Operation
---------------------------------------
---------------------------------------