Description
MEMORY ERROR
The thermostat memory settings are corrupted. To clear, load the factory defaults
in the Toolbox menu. The thermostat will not operate any heating or cooling
equipment while this error message is present.
INTERNAL ROOM SENSOR FAULT
Due to an open or short circuit, the thermostat is unable to read the internal room
temperature sensor. If sensor 1, 2 or 3 is set to room the thermostat continues to
operate, otherwise operation stops.
The error cannot be field repaired. Contact your tekmar sales representative for
warranty or repair procedures.
INTERNAL HUMIDITY SENSOR FAULT
Due to an open or short circuit, the thermostat is unable to read the internal
humidity sensor. The thermostat stops controlling the humidifier or dehumidifier
unless an external humidity sensor is installed on Sensor 3.
The error cannot be field repaired. Contact your tekmar sales representative for
warranty or repair procedures.
SENSOR 1 FAULT
Due to an open or short circuit, the thermostat is unable to read the sensor wired
to S1 and Com. The thermostat stops normal operation if sensor 1 is the only
active room or floor sensor or if a floor maximum temperature has been set.
Check the auxiliary sensor wire for short circuits according to the sensor installa-
tion manual. It may be necessary to replace the auxiliary sensor. Once the error
has been corrected, the error message automatically clears.
SENSOR 2 FAULT
Due to an open or short circuit, the thermostat is unable to read the sensor wired
to S2 and Com. The thermostat stops normal operation if sensor 2 is the only
active room or floor sensor or if a floor maximum temperature has been set.
Check the auxiliary sensor wire for short circuits according to the sensor installa-
tion manual. It may be necessary to replace the auxiliary sensor. Once the error
has been corrected, the error message automatically clears.
SENSOR 3 FAULT
Due to an open or short circuit, the thermostat is unable to read the sensor wired
to S3 and Com. The thermostat stops normal operation if sensor 3 is the only
active room sensor or if a floor maximum temperature has been set.
Check the auxiliary sensor wire for short circuits according to the sensor installa-
tion manual. It may be necessary to replace the auxiliary sensor. Once the error
has been corrected, the error message automatically clears.
When an error occurs an email notification will be sent to the registered mobile
account owner.
Error Messages