22 of 36
Setting
Range
Default
SENSOR 1
Select the type of sensor connected to S1 and Com
wiring terminals.
Off,
Room,
Floor
Off
SENSOR 2
Select the type of sensor connected to S2 and Com
wiring terminals.
Off,
Room,
Floor,
Outdoor
Off
SENSOR 3
Select the type of sensor connected to S3 and Com
wiring terminals.
Off,
Room,
Floor,
Humidity
Off
INTERNAL ROOM SENSOR
Select if the internal room temperature sensor is on or
off. Only available when Sensor 1, 2 or 3 is set to read a
room or floor sensor.
Off,
On
On
INTERNAL HUMIDITY SENSOR
Select if the internal humidity sensor is on or off. Only
available when Sensor 3 is set to read an external
humidity sensor.
Off,
On
On
ROOM OFFSET
Manual offset correction of the room temperature
measurement.
Off,
-5 to +5°F
-3.0 to 3.0°C
Off
FLOOR OFFSET
Manual offset correction of the floor temperature
measurement.
Off,
-5 to +5°F
-3.0 to 3.0°C
Off
HUMIDITY OFFSET
Manual offset correction of the relative humidity
measurement.
Off,
-10% to +10%
Off
Setup - Sensors
-----------------------------------------------------
-----------------------------------------------------