WARNING
This thermostat is a line voltage control (120 Volts to
240 Volts.) Do not install it if you are not completely
familiar with house wiring. If handled improperly,
there can be risk of a 120 Volt to 240 Volt electric
shock hazard, which may cause serious injury or
death.
CT62A,B
Line Voltage Electric Heat Thermostats
S.M. • Rev. 11-94 • ©Honeywell Inc. 1994 • Form Number 69-0829—1
Your Honeywell Thermostat
Your new Honeywell CT62 Electric Heating Thermostat
provides line voltage control of a radiant cable, electric
baseboard, and resistive-rated fan forced heaters within
the ratings listed above.
Installation Instructions
CT62A provides single-line break.
CT62B provides double-line break.
Temperature Range: 50
°
F to 80
°
F (10
°
C to 25
°
C)
Electrical Ratings: 60 Hz noninductive
22A at 120-240 Vac; 19A at 277 Vac
Do-It-Yourself models
3
REMOVE OLD THERMOSTAT
WARNING
Begin by turning off power to the heating circuit at
the main service panel.
Remove cover of old thermostat—cover normally
snaps off when pulled firmly from the bottom. If it
resists, check for a screw that locks the cover.
Loosen screws holding thermostat base to outlet
box and lift away.
Disconnect wires from old thermostat. As you
disconnect each wire, tape the end and label it with
the letter of the terminal designation to make reconnection
to new thermostat easier.
Check the old insulation for cracks, nicks or fraying,
and apply high quality plastic tape where necessary
for adequate insulation.
Retain the old thermostat for reference purposes
and until your new thermostat is functioning
smoothly.
1
PREPARATION
Proper installation of your Honeywell thermostat will
occur if you follow these instructions STEP-BY-
STEP. It is recommended that as you read, understand
and complete each step, you check
✓
it off with pencil or
pen.
Check thermostat suitability for your home’s system
by reviewing the ratings listed above.
Make certain that your heating system is working,
especially if it has been inoperative for a length of
time. If the system does not work, contact your local
electrician for assistance.
Carefully unpack your new thermostat. To avoid
damage to the sensing element, do NOT remove
the thermostat cover until wiring has been completed.
Save packages of screws, instructions, receipt and
proof-of-purchase.
THERMOSTAT MOUNTING
2
DIMENSIONS
M5795A
FRONT VIEW
SIDE VIEW
80
•
70
•
60
•
50
•
˚F
4-3/8
(111)
2-7/8 (73)
1-1/2
(39)
1-3/4
(48)
3/4
(19)
1/2 (13)
1/2 (13)
2-1/8
(54)
3-1/4
(83)