AM Series Boiler & Water Heater User Manual
CHAPTER 9
– OPERATION
OMM-0100_E
•
GF-146
•
11/15/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 114 of 170
Factory Menu
BOILER
PARAMETERS
WATER HEATER
PARAMETERS
PARA#
PARAMETER
DESCRIPTION
RANGE
FACTORY
SETTINGS
BURNER
1
BURNER
2 TO 4
BURNER
1
BURNER
2 TO 4
3002
Fan speed range
0 to 4
0
Refer to Table 8-1 in Chapter 8
3003
Display units
C = °C and bar units
F = °F and PSI units
F
F
F
F
F
3004
Water pressure sensor
0 = Disabled
1 = Enabled
2 = N/A
3 = N/A
1
1
0
1
0
3005
Burner
flapper valve
0 = Disabled
4 = Enabled
8 = N/A
12 = N/A
4
4
4
4
4
3006
Water
flow sensor
0 = Disabled
16 =
N/A
32 = N/A
48 = N/A
48
48
48
48
48
3007
Condensate blocked
drain detector
EnAb = Enabled
dISA = Disabled
Enab
Enab
dISA
Enab
dISA
3008
Flue gas detector
SEnS = Sensor
StCH = Switch
SEnS
SEnS
SEnS
SEnS
SEnS
3009
Outdoor thermistor type
10 = 10kohms
12 = 12kohms
10
10
10
10
10
3010
Other thermistor type
10 = 10kohms
12 = 12kohms
10
10
10
10
10
3011
Pump MODE
0 = Local pump
1 = N/A
2 = N/A
3 = N/A
0
0
0
0
0
3012
DHW mode
0 = no DHW
1 = DHW store with
sensor
2 = DHW store with
aquastat
3 = N/A
4 = N/A
5 = N/A
0
1
(if indirect
W.H. is
present)
0
0
0
3013
Reset Err 115
EnAb = Enabled
dISA = Disabled
Enab
Enab
Enab
Enab
Enab