AM Series Boiler & Water Heater User Manual
CHAPTER 9
– OPERATION
OMM-0100_E
•
GF-146
•
11/15/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 112 of 170
Installer Menu
Parameters
PAR#
DESCRIPTION
UM
RANGE
BOILER
FAC.SET
W.H.
FAC.SET
USER
2011
System test: Local pump (and of the Burner 1
Motorized valve)
\
On or OFF
OFF
OFF
2012
System test: CH pump
\
On or OFF
OFF
OFF
2013
System test: DHW pump
\
On or OFF
OFF
OFF
2014
Display test (when RESET button is pushed
all display icons will light-on. Next RESET
buttons back in settings menu)
\
\
\
\
2020
Warm weather shutdown temperature
°F
32 to 95
69
N/A
2021
Reset curve design: winter outdoor
°F
-4 to 41
24
N/A
2022
Reset curve design: winter supply
temperature
°F
32 to 176
176
N/A
2023
Reset curve design: spring outdoor
°F
32 to 86
69
N/A
2024
Reset curve design: spring supply
temperature
°F
32 to 104
104
N/A
2027
Night setback temperature
°F
2 to 90
18
N/A
2040
N/A
N/A
N/A
N/A
N/A
2041
N/A
N/A
N/A
N/A
N/A
2042
Burner 1 anti-cycling: time
sec
10 to 900
180
180
2043
Burner 1 anti-cycling: differential temperature
°F
0 to 36
28
28
2062
DHW post pump time
sec
10 to 255
240
N/A
2063
DHW max priority time
min
1 to 60
30
N/A
2067
DHW priority
0
= (TIME), DHW has priority to CH during
DHW max priority time (2063).
1
= (OFF), CH always has priority to DHW.
2
= (ON), DHW always has priority to CH.
2
N/A
2100
Display: delay to shut off
min
0 to 30
5
5
2101
MULTIBURNER Emergency mode (If sensor
1102 fail)
\
no or yes
Yes
Yes
2102
MULTIBURNER Emergency setpoint
°F
68 to 149
113
113
2103
MULTIBURNER start delay time
sec
1 to 900
180
15
2104
MULTIBURNER stop delay time
sec
1 to 900
180
15
2105
MULTIBURNER start burner diff.
°F
0 to 36
9
9
2106
MULTIBURNER stop burner diff.
°F
0 to 36
9
9
2107
MULTIBURNER calculated setpoint. Max
offset up.
°F
1 to 36
18
7
2108
MULTIBURNER calculated setpoint. Max
offset down.
°F
1 to 36
36
7
2109
MULTIBURNER next burner start rate
%
1 to 100
70
70
2110
MULTIBURNER next burner stop rate
%
1 to 100
10
10
2111
MULTIBURNER rotation interval
Days
0 to 9
6
6
2113
MULTIBURNER start modulation delay factor
min
0 to 60
5
0
2114
MULTIBURNER post local pump time
sec
0 to 255
240
240
2200
System test: all burners together.
\
Off, Low, Ign, High
OFF
OFF
2201
System test: Burner 1 (Master).
\
Off, Low, Ign, High
OFF
OFF
2202
System test: Burner 2.
\
Off, Low, Ign, High
OFF
OFF