AM Series Boiler & Water Heater User Manual
CHAPTER 7: INSTALLATION
– NATURAL GAS
OMM-0100_E
•
GF-146
•
11/15/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 87 of 170
7.3 Natural Gas Pipe Sizing
Refer to the table below for pipe lengths and diameters. For additional gas pipe sizing
information, refer to ANSI Z223.1 (or B149.1 for Canadian installations).
TABLE 7-1: Gas Pipe Capacity for Natural Gas
Iron Pipe Size (in)
Nominal:
3/4
1
1 1/4
1 1/2
2
2 1/2
3
4
Actual ID:
0.824
1.049
1.380
1.610
2.067
2.469
3.068
4.026
Length (ft
)
Capacity in Cubic Feet of Gas per Hour
10
273
514
1060
1580
3050
4860
8580
17500
20
188
353
726
1090
2090
3340
5900
12000
30
151
284
583
873
1680
2680
4740
9660
40
N/A
243
499
747
1440
2290
4050
8270
50
N/A
215
442
662
1280
2030
3590
7330
60
N/A
195
400
600
1160
1840
3260
6640
70
N/A
179
368
552
1060
1690
3000
6110
80
N/A
167
343
514
989
1580
2790
5680
90
N/A
157
322
482
928
1480
2610
5330
100
N/A
148
304
455
877
1400
2470
5040
125
N/A
131
269
403
777
1240
2190
4460
150
N/A
119
244
366
704
1120
1980
4050
175
N/A
N/A
224
336
648
1030
1820
3720
200
N/A
N/A
209
313
602
960
1700
3460
250
N/A
N/A
185
277
534
851
1500
3070
NOTE:
Maximum pipe capacity is based on a 0.60 specific gravity gas at a pressure of 0.5 PSIG and
a 0.3” W.C. pressure drop.
7.4 Natural Gas Supply Pressure Requirements
•
Install 100% lockup gas pressure regulator in supply line if inlet pressure can exceed
13”W.C. at any time. Adjust lockup regulator for 13” W.C. maximum.
•
Pressure required at the gas valve inlet pressure port:
o
Maximum 13” W.C. with no flow (lockup) or with appliance off.
o
Minimum 3” W.C. with gas flowing (verify during high fire).
7.5 Propane Gas Pipe Sizing
Contact gas supplier to size pipes, tanks, and 100% lockup propane gas pressure regulator.
7.6 Propane Gas Supply Pressure Requirements
•
Adjust propane supply regulator provided by the gas
supplier for 13”W.C. maximum
pressure.
•
Pressure required at the gas valve inlet pressure port:
o
Maximum 13” W.C. with no flow (lockup) or with appliance off.
o
Minimum 3” W.C. with gas flowing (verify during high fire).