AM Series Boiler & Water Heater User Manual
CHAPTER 9
– OPERATION
OMM-0100_E
•
GF-146
•
11/15/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 113 of 170
Installer Menu
Parameters
PAR#
DESCRIPTION
UM
RANGE
BOILER
FAC.SET
W.H.
FAC.SET
USER
2203
System test: Burner 3.
\
Off, Low, Ign, High
OFF
OFF
2204
System test: Burner 4.
\
Off, Low, Ign, High
OFF
OFF
9.17 Factory Menu
Inappropriate changes to parameters in the Factory Menu could result in a unit or system
malfunction.
For this reason, only a qualified technician who has in-depth knowledge of the unit
should make any changes to the parameters in this menu. The parameters available allow the
unit to be configured and set for proper operation.
The Factory Menu for boilers and water heaters are different from one another, so there are
separate columns showing the settings for each in the chart below.
To enter the Factory Menu, perform the following steps:
Factory Menu Navigation and Adjustment
1.
Turn the electrical power switch to
OFF
.
2.
Simultaneously press and hold the
RESET
and
buttons.
3.
While the
RESET
and
buttons are both depressed, turn the power switch to ON.
4.
Wait until the word “init” is displayed in the control panel display, or until the control panel
display begins to show the 3000 parameters, then release the RESET button and then the
button.
5.
Press the
and
buttons to scroll up or down through the parameters.
6.
To change a displayed parameter, press the
RESET
button. The parameter value will blink.
7.
Press the
and
buttons to cycle up or down through the parameter values.
8.
To set a parameter value, press the
RESET
button while the desired value is displayed.
9.
Wait at least 10 seconds after the last parameter change before exiting menu.
10.
Exit the menu by turning the unit power switch to
OFF
.
11.
The power switch may now be turned
ON
, and the Factory Menu will no longer be
displayed.
Factory Menu
BOILER
PARAMETERS
WATER HEATER
PARAMETERS
PARA#
PARAMETER
DESCRIPTION
RANGE
FACTORY
SETTINGS
BURNER
1
BURNER
2 TO 4
BURNER
1
BURNER
2 TO 4
3001
Burner logic address
NOTE
: This is
NOT
the
Modbus address
0 = No cascade
1 = Burner 1 (Master)
2 to 4 = Burner
2 to
4 (slave burners)
2
1
2 to 4
1
2 to 4