AM Series Boilers and Water Heaters User Manual
CHAPTER 10
– MAINTENANCE
OMM-0100_E
•
GF-146
•
11/15/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 124 of 170
SECTION 10:
MAINTENANCE
This section must be brought to the attention of the user by the installer so that the user can
make the necessary arrangements with a qualified service agency for the periodic care and
maintenance of the boiler. Refer to Table 10-1 for a schedule of necessary maintenance
procedures.
Lack of proper care and maintenance of this boiler and any fuel burning equipment may result in
a hazardous condition.
A trained and qualified service technician should perform the inspection listed in these
instructions before each heating season and at regular intervals.
CAUTION!
Servicing, inspection and adjustment must be done by a trained technician in accordance
with all applicable local and national codes. Improper servicing or adjustment could damage
the boiler and result in equipment damage or a dangerous condition!
Table 10-1: AM Series Maintenance Schedule
SERVICE TECHNICIAN
USER MAINTENANCE
Annual Startup and Maintenance:
•
Address reported problems
•
Check all piping for gas leaks
•
Verify
fl
ue and air lines in good condition and sealed tight
•
Check system water pressure/system piping/expansion tank
•
Check control settings
•
Check ignition and
flame
sense electrodes
•
Check wiring and connections
•
Perform start up checkout and performance
verification
•
Flame inspection
•
Check
fl
ame signal
•
Inspect combustion chamber. Clean and vacuum if necessary.
•
Clean the heat exchanger if
the flue temperature
is 63°F (35°C)
above return water temperature
•
Clean condensate reservoir and
fi
ll with fresh water
•
Clean air
fi
lter
•
Check the capacity input
•
Check relief valve
•
Check thermal Insulation inside every module
Daily Check:
•
Check boiler area
•
Check pressure gauge
Monthly Check:
•
Check vent piping and vent termination screen
•
Check air piping and air termination screen
•
Check relief valve
•
Check condensate drain system
•
Check any air vents on the system that no leaks
are present
Periodic Check:
•
Test low water cut-off (if used)
•
Reset low water cut-off button (if used)
Six Month Check:
•
Check boiler piping (gas and water) for leaks
•
Check and clean anodes in buffer tank (if installed)
End of Season Months Check:
•
Shut boiler down (unless boiler used for domestic
hot water)