AM Series Boiler & Water Heater User Manual
CHAPTER 6: INSTALL
– VENT & COMBUSTION AIR PIPING
OMM-0100_E
•
GF-146
•
11/15/2019
Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page 71 of 170
6.5.4 Air Intake and Vent Starter Pieces
Venting must be supported per guidelines listed in the National Mechanical Code, Section 305,
Table 305.4 or as local codes dictate.
Figure 6-2 shows how the air intake and vent outlet adapters are assembled. To connect a vent
pipe to the air intake and vent outlets, proceed as follows while referring to Figures 6-2 and 6-3:
Installing the Air Intake and Vent Connections
1.
Apply a suitable sealant (Viton RTV or equivalent) to the inside diameter of both the air inlet
adapter and vent outlet adaptor (see Figure 6-2) to create an airtight seal with the piping.
2.
Install air inlet piping and exhaust vent piping
3” deep into the adapters.
3.
Tighten each adaptor hose clamp (Fig. 6-2) to secure each adaptor to its respective piping.
4.
Drill a 1/4” hole into the exhaust outlet piping in approximately the position as shown in
Figure 6-2. This port will be used as a combustion analysis port during the combustion
calibration procedure described in Section 8.2. Procure a suitable cap to plug this port when
it is not being used for calibration.
WARNING!
You must ensure that a suitable cap is used to seal the calibration analysis port during
normal operation to prevent the escape of dangerous exhaust gases.
Figure 6-2: Air Intake and Vent Connection Installation
BOLTS
EXHAUST OUTLET
ADAPTOR
ADAPTOR GASKET
EXHAUST CHIMNEY
EXHAUST SEAL
GASKET FITS INTO
INNER GROOVE OF FLUE
EXHAUST CHIMNEY
STEP 2:
EXHAUST
OUTLET PIPING
(FIELD PROVIDED)
ADAPTOR
GASKET
AIR INLET
ADAPTOR
STEP 3:
HOSE
CLAMP
BOLTS
STEP 2:
AIR INLET
PIPING (FIELD
PROVIDED)
COMBUSTION ANALYSIS
PORT (FIELD INSTALLED)
STEP 4:
CAP (FIELD PROVIDED)
AIR
INLET
STEP 1:
VITON RTV
ADHESIVE
EXHAUST SEAL
GASKET