Watlow PM PLUS™ 6
• 45 •
Chapter 5: Setup
Setup List
Setup Lists
You will not see every parameter listed here. These vary depending on the features enabled on your device.
Analog Input List
Operations — Setup — Analog Input
Parameter
Description
Range of Options
Default
ID*
Analog Input [1,2]
The process value of the input. Select instance
1 or 2 if there are two input instances. (With-
out two analog input instances, Analog 1 will
be automatically selected/displayed and Analog
2 will not appear).
Note: Ensure that there is no Input Error (61)
when reading this value using a field bus proto-
col. If an error exists, the last known value prior
to the error will be returned.
-1,999.000 to 9,999.000°F
or units
-1,128.000 to 5,537.000°C
- - - -
4001
Operations — Setup — Analog Input — [Analog Input 1, Analog Input 2]
Sensor Type
Analog sensor type wired to this input.
Note: There is no open sensor protection for
process inputs.
Off (62)
Thermocouple (95)
Millivolts (56)
Volts dc (104)
Milliamps dc (112)
RTD 100 Ω (113)
RTD 1,000 Ω (114)
Potentiometer 1 kΩ (155)
Thermistor (229)
Thermocouple
or Thermistor
4005
TC Linearization
Thermocouple linearization wired to this input. B (11)
K (48)
C (15)
N (58)
D (23)
R (80)
E (26)
S (84)
F (30)
T (93)
J (46)
J
4006
RTD Leads
Quantity of leads on the RTD wired to this
input.
2 (1)
3 (2)
2
4007