Watlow PM PLUS™ 6
• 56 •
Chapter 5: Setup
Setup Lists
You will not see every parameter listed here. These vary depending on the features enabled on your device.
Maximum Manual
Power
Maximum value of the open-loop set point
range.
-100.0 to 100.0%
100
7006
Manual Power *
Fixed level of output power when in manual
(open-loop) mode.
-100.0 to 100.0% (heat
and cool) 0 to 100.0%
(heat only)
-100.0 to 0% (cool only)
0.0
7002
Control Mode *
Method that this loop will use to control.
Off (62)
Auto (10)
Manual (54)
Auto
8001
Output List
Operations — Setup — Output —
Output 1,2,3,4
Select the output instance to configure
1,2,3,4
1
Operations — Setup — Output — Output [1,2,3,4] —
Function
Output Digital (1 to 4). Select what function
will drive this output.
Note: When digit 9 in the part number = L, out-
put 4 is always fixed as a limit function. In addi-
tion, only output 3 can be programmed as a limit
function.
Off (62)
Alarm (6)
Heat (36)
Cool (20)
Special Function Output 1
(1532)
Special Function Output 2
(1533)
Timer Event 1 (1951)
Timer Event 2 (1952)
Timer Event 3 (1953)
Profile Event Out A (233)
Profile Event Out B (234)
Limit (126)
Output 1 -
Heat
Output 2 -
Alarm
Output 3 - Off
Output 4 - Off
6005
Output Function In-
stance
Output Digital (1 to 4). Set the instance of the
function selected.
1 to 4
1
6006
Time Base Type
Output Digital (1 to 4). Set the time base type.
This parameter is only used with PID control,
but can be set anytime.
Fixed Time Base (34)
Variable Time Base (103)
Fixed Time
Base
6002
Fixed Time Base
Output Digital (1 to 4). Set the time base for
fixed-time-base control.
1.0 to 60.0 seconds (solid-
state relay or switched dc)
5.0 to 60.0 seconds (me-
chanical relay or NO-ARC
power control)
1.0 sec. for
SSR or swdc
5.0 for relay