Watlow PM PLUS™ 6
• 121 •
Chapter 10 Appendix
CIP Implicit Assembly
Target (PM PLUS) to Originator (Master)
Assembly
Members
Assembly
Class, Instance,
Attribute
Data
Type
Parameter
Parameter
Class, Instance,
Attribute
PLC
Data Type
- - - -
Cannot be changed
Binary
Device Status
None
BIN
1
0x77, 0x02, 0x01
DINT
Analog Input 1, Analog Input Value
0x68, 0x01, 0x01
REAL
2
0x77, 0x02, 0x02
DINT
Analog Input 1, Input Error
0x68, 0x01. 0x02
REAL
3
0x77, 0x02, 0x03
DINT
Analog Input 2, Analog Input Value
0x68, 0x02, 0x01
REAL
4
0x77, 0x02, 0x04
DINT
Analog Input 2, Input Error
0x68, 0x02, 0x02
REAL
5
0x77, 0x02, 0x05
DINT
Alarm 1, Alarm State
0x6D, 0x01, 0x09
DINT
6
0x77, 0x02, 0x06
DINT
Alarm 2, Alarm State
0x6D, 0x02, 0x09
DINT
7
0x77, 0x02, 0x07
DINT
Alarm 3, Alarm State
0x6D, 0x03, 0x09
DINT
8
0x77, 0x02, 0x08
DINT
Alarm 4, Alarm State
0x6D, 0x04, 0x09
DINT
9
0x77, 0x02, 0x09
DINT
Event Status 1
0x6E, 0x01, 0x05
DINT
10
0x77, 0x02, 0x0A
DINT
Event Status 2
0x6E, 0x02, 0x05
DINT
11
0x77, 0x02, 0x0B
DINT
Loop 1 - Control Mode Active
0x97, 0x01, 0x02
DINT
12
0x77, 0x02, 0x0C
DINT
Loop 1 - Heat Power
0x97, 0x01, 0x0D
REAL
13
0x77, 0x02, 0x0D
DINT
Loop 1 - Cool Power
0x97, 0x01, 0x0E
REAL
14
0x77, 0x02, 0x0E
DINT
Limit State
0x70, 0x01, 0x06
DINT
15
0x77, 0x02, 0x0F
DINT
Profile Start
0x7A, 0x01, 0x01
DINT
16
0x77, 0x02, 0x10
DINT
Profile Action Request
0x7A, 0x01, 0x0B
DINT
17
0x77, 0x02, 0x11
DINT
Current Profile
0x7A, 0x01, 0x03
DINT
18
0x77, 0x02, 0x12
DINT
Current Step
0x7A, 0x01, 0x04
DINT
19
0x77, 0x02, 0x13
DINT
Loop 1 - Active Set Point
0x7A, 0x01, 0x05
REAL
20
0x77, 0x02, 0x14
DINT
Step Time Remaining
0x7A, 0x01, 0x09
DINT
21
0x77, 0x02, 0x15
DINT
None Specified
- - - -
- - - -
22
0x77, 0x02, 0x16
DINT
None Specified
- - - -
- - - -
23
0x77, 0x02, 0x17
DINT
None Specified
- - - -
- - - -
24
0x77, 0x02, 0x18
DINT
None Specified
- - - -
- - - -
25
0x77, 0x02, 0x19
DINT
None Specified
- - - -
- - - -
26
0x77, 0x02, 0x1A
DINT
None Specified
- - - -
- - - -
27
0x77, 0x02, 0x1B
DINT
None Specified
- - - -
- - - -
28
0x77, 0x02, 0x1C
DINT
None Specified
- - - -
- - - -
29
0x77, 0x02, 0x1D
DINT
None Specified
- - - -
- - - -
30
0x77, 0x02, 0x1E
DINT
None Specified
- - - -
- - - -
31
0x77, 0x02, 0x1F
DINT
None Specified
- - - -
- - - -
32
0x77, 0x02, 0x20
DINT
None Specified
- - - -
- - - -
33
0x77, 0x02, 0x21
DINT
None Specified
- - - -
- - - -
34
0x77, 0x02, 0x22
DINT
None Specified
- - - -
- - - -
35
0x77, 0x02, 0x23
DINT
None Specified
- - - -
- - - -
36
0x77, 0x02, 0x24
DINT
None Specified
- - - -
- - - -
37
0x77, 0x02, 0x25
DINT
None Specified
- - - -
- - - -
38
0x77, 0x02, 0x26
DINT
None Specified
- - - -
- - - -
39
0x77, 0x02, 0x27
DINT
None Specified
- - - -
- - - -
40
0x77, 0x02, 0x28
DINT
None Specified
- - - -
- - - -
The first T to O member above (Device Status) is always present but not counted when configuring the
gateway size using the RUI or EZ-ZONE Configurator software. However, it most always be counted
when configuring the input size of the Master. As an example, if using the DINT comm format in a PLC
and the entire assembly as shown above, the input size would require 41 members.
Although 40 members are built into PM controllers, the RUI allows for a maximum of 20.