D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
124
Low Deviation Function
l
01 LoDeviation
r
func
b
off
Choose whether the alarm functions as an alarm or as a boost output, or disable the alarm.
Table 6.14 – Alarm Functions on page 122
Default:
off
DeviceNet™ Object:
See
Alarm Enable on page 133 and Alarm Function on page 134.
Low Deviation Output
l
01 LoDeviation
r
output
b
none
Choose a digital output to activate when the low deviation alarm occurs. You cannot choose an
output that is in use for closed-loop control or for the Serial DAC clock.
Values:
none
(0) or output 1 to 18 (1 to 18). Values in parentheses are for communications.
Default:
none
(0)
DeviceNet™ Object:
Alarm (67 hex)
Alarm Low Set Point
l
01 Alarm low
r
SP
b
0 ˚C
Enter the set point at which the low alarm activates. The low alarm activates if the process variable
drops below this value. For more information, see Process Alarms on page 75.
Values:
For a thermocouple or RTD input, any value within the input range (see
Types and Ranges on page 107). For a process input, any value between the
Input range low
and
Input range high
parameters.
Default:
0
Decimal Placement for DeviceNet™:
See Decimal Placement for Numeric Values on page 46.
DeviceNet™ Object:
Alarm (67 hex)