D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
101
Table 6.3
– Values for BCD Job Load
DISPLAY
VALUE
DeviceNet™
VALUE
DESCRIPTION
use D/I 1
1
Use digital input 1 for remote selection of jobs 1 and 2.
use D/I 1-2
2
Use digital inputs 1 and 2 for remote selection of jobs 1 to 4.
use D/I 1-3
3
Use digital inputs 1 to 3 for remote selection of jobs 1 to 8.
disabled
0
Disable remote job selection.
BCD Job Load Logic
l
BCD job load
r
logic
b
1=true
Choose which state is considered “true” for the digital inputs that are used for remote job selection.
• If
1=true
is selected, then an input is true if connected to controller common, and false for an
open circuit.
• If
0=true
is selected, then an input is true for an open circuit, and false if connected to
controller common.
Table 6.4 shows which combinations of input states are required to load each job.
Values:
1=true (0) or 0=true
(1). Values in parentheses are for communications.
Default:
1=true
(0)
DeviceNet™ Object:
Global (6B hex)
Table 6.4
– Digital Input States Required to Load Each Job
JOB
DIGITAL INPUT
1
2
3
1
F
F
F
2
T
F
F
3
F
T
F
4
T
T
F
5
F
F
T
6
T
F
T
7
F
T
T
8
T
T
T