D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
122
Table 6.14
– Alarm Functions
VALUE
DESCRIPTION
off
No alarm function.
standard
Alarm is indicated and logged.
Latching global alarm is activated.
Alarm must be acknowledged to clear.
Optional non-latching alarm output is activated.
boost
Alarm message on controller display only.
Alarm does not require acknowledgement.
Non-latching alarm output is activated. Use the alarm set
points to control this output for boost control.
Alarm High Output
l
01 Alarm high
r
output
b
none
Choose a digital output to activate when the high alarm occurs. You cannot choose an output that is
in use for closed-loop control or for the Serial DAC clock.
Values:
none
(0) or output 1 to 18 (1 to 18). Values in parentheses are for communications.
Default:
none
(0)
DeviceNet™ Object:
Alarm (67 hex)
High Deviation Value
l
01 HiDeviation
r
value
b
5 ˚C
Enter the amount by which the process variable must rise above the set point for the high deviation
alarm to occur. For more information, Deviation Alarms on page 76
Table 6.12 – Values for the Control Hysteresis and Deviation Alarm Parameters on page
Default:
See Table 6.12.
DeviceNet™ Object:
Alarm (67 hex)