D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
123
High Deviation Function
l
01 HiDeviation
r
func
b
off
Choose whether the alarm functions as an alarm or as a boost output, or disable the alarm.
Table 6.14 – Alarm Functions on page 122
Default:
off
DeviceNet™ Object:
High Deviation Output
l
01 HiDeviation
r
output
b
none
Choose a digital output to activate when the high deviation alarm occurs. You cannot choose an
output that is in use for closed-loop control or for the Serial DAC clock.
Values:
none
(0) or output 1 to 18 (1 to 18). Values in parentheses are for communications.
Default:
none
(0)
DeviceNet™ Object:
Alarm (67 hex)
Low Deviation Value
l
01 LoDeviation
r
value
b
5 ˚C
Enter the amount by which the process variable must fall below the set point for the low deviation
alarm to occur. For more information, Process Alarms on page 75.
Values:
Table 6.12 – Values for the Control Hysteresis and Deviation Alarm Parameters on page
115 for values and decimal placement.
Default:
Table 6.12
DeviceNet™ Object:
Alarm (67 hex)