D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
121
Alarms Menu
l
01 Alarms
r
Other menus
b
Use the Alarms menu to configure high alarms, low alarms, and deviation alarms, including:
• Alarm set points
• Alarm outputs
• Alarm behavior
• Alarm hysteresis
• Alarm delay
Alarm High Set Point
l
01 Alarm high
r
SP
b
760 ˚C
Enter the set point at which the high alarm activates. The high alarm activates if the process variable
rises above this value. For more information about the high alarm, Alarm High and Alarm Low on
page 76
Values:
For a thermocouple or RTD input, any value within the input range (Table 6.7 – Input Types
and Ranges on page 107). For a process input, any value between the
Input range low
and
Input
range high
parameters.
Default:
760. Decimal placement depends upon the
Input type
and
Disp format
settings.
Decimal Placement for DeviceNet™:
Decimal Placement for Numeric Values on page 46
DeviceNet™ Object:
Alarm (67 hex)
Alarm High Function
l
01 Alarm high
r
func
b
off
Choose whether the high alarm functions as an alarm or as a boost output, or disable the alarm.
Values:
See Table 6.14 below.
Default:
off
DeviceNet™ Object:
See Alarm Acknowledge on page 133 and Alarm Function on page 134.