CLS200 Series User’s Guide
Chapter 2: Installation
29
Power Connections
This section covers making the power connections to the CLS200 and connecting the TB50.
TB1
Sensor Inputs
Serial Communication
TB18
Digital Inputs
Digital Outputs
Pulse Input
TB2
Power Input
Figure 2.10
— CLS200 Series Controller with TB18
TB1
Sensor Inputs
Serial Communication
SCSI to TB50
Digital Inputs
Digital Outputs
Pulse Input
TB2
Power Input
Figure 2.11
— CLS200 Series Controller with TB50
Wiring the Power Supply
WARNING!
Use a power supply with a Class 2 rating only. UL
®
approval requires a
Class 2 power supply.
Connect power to the controller before any other connections, This allows you to ensure that the
controller is working before any time is taken installing inputs and outputs.
Table 2.2
—
Power Connections
FUNCTION
POWER SUPPLY
CLS200 TB2
DC Power (Controller)
+12 to 24VDC
+
DC Common
12 to 24VDC Common
–
Earth Ground
Ground
1. Connect the dc common terminal on the power supply to the dc common (-) terminal on
CLS200 TB2.
2. Connect the positive terminal on the power supply to the dc positive (+) terminal on
CLS200 TB2.
3. If using an isolated dc output or another power supply to power the loads, connect the dc
common of the supply powering the loads to the dc common of the supply powering the
controller.