CLS200 Series User’s Guide
Chapter 4: Setup
68
ALARM
LOAD SETUP
FROM JOB? 1
Selectable values:
1
to
8
The following parameters are loaded for each loop as part of a job:
• PID constants, filter settings, setpoints and spread values.
• Loop control status (automatic or manual) and output values (if the loop is in manual control)
• Alarm function (off, alarm control) setpoints, high/low process setpoints, high/low deviation
setpoints and deadband settings, and loop alarm delay.
If you have enabled the remote job select function (see J
ob Select Digital Inputs
below), you will not
be able to load a job. If you try, you will see this message:
ALARM
CANNOT LOAD JOB
REMOTE SELECT ON
Save Setup to Job
Save the job information for every loop to one of eight jobs in the battery-backed RAM.
ALARM
SAVE SETUP
TO JOB? 1
Selectable values:
1
to
8
If you have enabled the remote job select function (see
Job Select Digital Inputs
below), you will not
be able to save a job. If you try, you will see this message:
ALARM
CANNOT SAVE JOB
REMOTE SELECT ON
Job Select Digital Inputs
Set the number of job select inputs. The controller uses these inputs as a binary code that specifies
the job number to run. The number of inputs you choose in this parameter controls the number of
jobs you can select remotely.
If you select
NONE
, digital inputs do not affect job selection. Jobs may be loaded and saved using
the
LOAD SETUP FROM JOB
and
SAVE SETUP TO JOB
parameters.