CLS200 Series User’s Guide
Chapter 2: Installation
20
CLS200 with SCSI Digital I/O
SCSI Connector
SCSI Cable
CLS200 with TB18 Digital I/O
TB50 Accessory Board
TB18 allows connection to...
11 Outputs for Control & Alarms
2 Digital Inputs
1 Pulse Input
TB50 allows connection to...
35 Outputs for Control & Alarms
8 Digital Inputs
1 Pulse Input
Sensor Inputs
Sensor Inputs
Figure 2.1
— CLS200 System Components
Mounting Controller Components
Install the controller in a location free from excessive heat (below 50ºC [122°F]), dust, and
unauthorized handling. Electromagnetic and radio frequency interference can induce noise on
sensor wiring. Select locations for the CLS200 and TB50 such that wiring can be routed clear of
sources of interference such as high voltage wires, power switching devices and motors.
NOTE!
For indoor use only.
WARNING!
To reduce the risk of fire or electric shock, install the CLS200 in a controlled
environment, relatively free of contaminants.
Recommended Tools
Use any of the following tools to cut a hole of the appropriate size in the panel.
• Jigsaw and metal file, for stainless steel and heavyweight panel doors.
• 1/8-DIN rectangular punch for most panel materials and thicknesses.
• Nibbler and metal file, for aluminum and lightweight panel doors.