CLS200 Series User’s Guide
Chapter 6: Ramp/Soak
122
Segment Events Output States
Assign a state to the event. At the end of the segment, the output goes to the state you assign here.
This parameter appears only if you answered
YES
to
EDIT SEG EVENTS?
ALARM
A SEG20 EV3 DO 30
ACTIVE STATE? OFF
Selectable values:
OFF
(high) or
ON
(low).
Edit Segment Triggers
Each segment may have up to two triggers (digital inputs). Both triggers must be true in order for the
segment to run. If a trigger is not true, the profile goes into the trigger wait state.
ALARM
A SEGMENT 15
EDIT SEG TRGGRS?
Press
YES
to edit triggers for the current segment, or
NO
to advance to the
SEGMENT TOLERANCE
parameter.
Trigger Input Number
Assign a digital input to a segment trigger. You can assign any digital input to any trigger. You can
also assign the same digital input as a trigger in more than one segment and more than one profile.
This parameter appears only if you answered
YES
to
EDIT SEG TRGGRS?
ALARM
A SEG 15 TRIG 1
INPUT NR ? NONE
Selectable values:
Any digital input from
1
to
8
, or
NONE
(disable trigger).
When you are done editing segment triggers, press
BACK
to return to
EDIT SEG TRGGRS
.
Trigger Active State
Choose the state that will satisfy the trigger condition. A trigger input is
ON
when pulled low by an
external device. A trigger input is
OFF
when the digital input is high.
This parameter appears only if you answered
YES
to
EDIT SEG TRGGRS?
ALARM
A SEG01 TR1 DIO8
ACTIVE STATE?OFF
Selectable values:
OFF
or
ON
.