![Watlow CLS200 User Manual Download Page 45](http://html1.mh-extra.com/html/watlow/cls200/cls200_user-manual_3708024045.webp)
CLS200 Series User’s Guide
Chapter 2: Installation
45
Table 2.10
—
EIA/TIA-232 Connections
WIRE COLOR
CLS200 TB1
DB 9 CONNECTOR
DB 25 CONNECTOR
White
TX Pin 26
RX Pin 2
RX Pin 3
Red
RX Pin 25
TX Pin 3
TX Pin 2
Black
GND Pin 23
GND Pin 5
GND Pin 7
Green
GND Pin 24
N/U Pin 9
N/U Pin 22
Shield
N/C
GND Pin 5
GND Pin 7
Jumpers in EIA/TIA-232 Connectors
Some software programs and some operator interface terminals require a Clear to Send (CTS) signal
in response to their Request to Send (RTS) signal, or a Data Set Ready (DSR) in response to their
Data Terminal Ready (DTR). The CLS200 is not configured to receive or transmit these signals. To
use such software with the CLS200, jumper the RTS to the CTS and the DTR to the DSR in the DB
connector. Table 2.11 lists the standard pin assignments for DB-9 and DB-25 connectors.
Table 2.11
—
RTS/CTS Pins in DB-9 and DB-25 Connectors
DB-9
DB-25
RTS
7
4
CTS
8
5
DTR
4
20
DSR
6
6
Cables manufactured by Watlow for EIA/TIA-232 communications include these jumpers.