background image

4211-1661   01/28/2022

APPENDIX: SYSTEM INSTALLATION

APPENDIX: SYSTEM INSTALLATION

page  2           

The WATERWORKS Steam Generator can be hung on a wall or set on it’s base. The best mounting location  

will satisfy all or most of the following conditions:

 

1. The steam line should slope to allow condensation to drain into the steam room.

2. The steam line should be less than 20 ft (6m) long; 10 ft (3m) is preferred. Steam lines over 20 ft (6m) long should be insulated.

3. The mounting location should minimize the number of bends and elbows in the steam line.

4. The steam line should enter the room 18” (460 mm) above the floor or at least 12” (305 mm)above a tub rim or ledge.

5

. No steam head shall be more than 30 inches (760 mm) above the floor.

6. The steam outlet should be located to avoid potential user contact.

7. The steamers should be installed in a dry, well ventilated area. The space provided should be at least: 

        7 cu ft (0,2m

3

) for one steamer or 17 cu ft (0,5m

3

)for two steamers or 27 cu ft (0,8m

3

) for three.

    Suggested locations are under a vanity or in a closet, attic, crawl space or basement. Note: 

The steamer must be in an area protected from freezing

8. The slave steamers should be installed within a 25 ft (7,6m) cable length of the primary steamer and the secondary steamer(s) should be within a 25 ft (7,6m) 

    cable length of the control installation.   

 

    Note: 

Longer control and slave cables are available; contact Service at 1-800-927-2120, Ext 3 for assistance

. The installation 

              should provide clearance for service and element removal. See diagram 3. 

 

10. The mounting location should allow for a drain hookup. There should be no more than three 90° bends and 10 ft (3m) of pipe between any steamer’s drain  

      outlet and its drain valve inlet. See diagram 

15

.

11.

 Refer to the mounting instructions in WATERWORKS installation instructions document 4211-1661 for details regarding mounting individual steamers.

 

SECTION  2:  SELECT MOUNTING LOCATION (continued)

IMPORTANT

Before deciding on a mounting location, 

please read through these installation

instructions completely and take a careful

look at al of the diagrams.

An exhaust fan installed outside the

steam room is strongly recommended

in order to remove excess steam

from the steambath or shower area

It is strongly recommended that no exhaust

fan be installed inside the steam room. Doing

so will result in a loss of heat and steam

through the exhaust fan and port.

Insulate all steam lines and drain lines

within the enclosed space.

Each steamer must be provided with

at least six (6) inches for wiring

access at the control wiring end.

Each steamer must be provided with at least fifte

en 

(15) inches clearance at 

the pipe end.

There should be at least thirty-six (36) inches

in front of the louvered cover at

each steamer for service access.

DIAGRAM 1: SERVICE CLEARANCE

36” (0,9 m) MIN

SERVICE CLEARANCE

15” (380 mm)

SERVICE CLEARANCE 

MINIMUM

6” (150 mm) MIN

SERVICE CLEARANCE

6” (150 mm) MIN

SERVICE CLEARANCE

WARNING

! Do not put a shut-off valve in the steam line! 

  The line must be unrestricted from the steamer into the steam room !  

  To reduce the risk of explosion, do not interconnect steam outlets!

• Do not mount outdoors. 

• Protect from freezing. 

• Unit must be located so as to allow access for service. 

• The steam steamer will not operate properly unless it is mounted level with the arrows pointed up. 

• A separate line must be provided or each steam outlet. 

• Avoid traps and valleys where water could collect and cause a steam blockage.| 

• The hot steam must be insulated against  user contact. Install the steam head so as to avoid potential 

  user  contact. 

• Do not install the steam head near benches or where condensation will drip on the user or puddle as 

  this will present a scald hazard. 

• The pressure relief valve must be installed in manner that reduces the risk of scalding.  

• Do Not drain the pressure valve or steamer into the steam room!  

• Draining the pressure relief valve into the steam room may present a scald hazard!

Refer to the following diagrams for some suggested systems (and some not allowable steam pipings).

Summary of Contents for WWSU08

Page 1: ...teamer should be the primary unit Each steamer should have its own automatic drain For commercial use we recommend checking with your local inspectors to confirm the steamer system is acceptable for y...

Page 2: ...age Important Safety Instruction 3 6 1 Mounting the Generator 7 8 2 Water Quality Requirements 8 3 Plumbing Instructions 9 12 4 Wiring Instructions 12 Electrical Information Chart 13 5 Bath Control In...

Page 3: ...ng must be installed by a licensed plumber in accordance with all applicable local and national codes Install indoors only Protect from freezing Generator must be level side to side and end to end The...

Page 4: ...erie doit tre install par un plombier sous licence conform ment tous les codes locaux et nationaux applicables Installer l int rieur uniquement Prot ger du gel G n rateur doit tre mise niveau lat rale...

Page 5: ...ERVICE INSTRUCTIONS 4211 1661 Rev A 01 28 2022 Page 5 of 17 POST WARNING LABEL OUTSIDE STEAMBATH FOR SAFETY WARNINGS tiquette d avertissement Ext rieur poste baiin de vapeur pour les avertissements re...

Page 6: ...utilis par toute personne y compris les enfants avec toutes leurs capacit s physiques sensorielles ou mentales ou qui manquent d exp rience ou de connaissances moins qu ils aient la supervision ou de...

Page 7: ...ervice Provide clearance for plumbing and electrical service and for element removal See Diagram 1 6 The steam line should slope to allow condensation to drain The mounting location should minimize th...

Page 8: ...ale to form on the internal surfaces This deposit or scale can interfere with the equipment s proper operation and even cause premature boiler or generator failure Concentration of impurities is gener...

Page 9: ...ator to allow for future servicing if needed and for emergency shut off Make sure the shut off is open providing water to the generator before turning it on IMPORTANT Water pressure required 20 100 ps...

Page 10: ...5 mm hole for the steam line entry Center the 1 2 copper steam pipe in the hole See Diagram 4 Terminate the steam line with a 1 2 NPT male adapter Stub the line out into the room 3 8 9 5 mm from the f...

Page 11: ...t have a drain valve installed to allow draining the tank for cleaning and maintenance A manual ball valve is supplied An electronic ball valve is available in the ADK Autodrain option When installed...

Page 12: ...dicated on the wire diagram for your voltage and phase This may require moving factory installed jumper Do not change the steamer s internal jumpers or wiring Only the supply wiring side of the termin...

Page 13: ...240 208 230 240 WWSU08 208 36 50 240 30 31 40 40 WWSU11 208 18 36 30 50 240 44 46 60 60 WWSU15 208 24 42 30 60 240 20 36 21 38 30 50 30 50 Nominal Amps at operating VAC 3 phz Recommended Breaker Mode...

Page 14: ...room The K3 and KT3 controls have a short tube on the back to help locate the control and to protect the cable end All of these controls connect to the steam generator s circuit board through Waterwor...

Page 15: ...or leaks 2 After the tank has filled to a safe level the heating elements will turn on Allow about 10 minutes for the steam to appear in the steam room 3 Once the steam is visible use the control to t...

Page 16: ...INSTALLATION AND SERVICE INSTRUCTIONS 4211 1661 Rev A 01 28 2022 Page 16 of 17...

Page 17: ...INSTALLATION AND SERVICE INSTRUCTIONS 4211 1661 Rev A 01 28 2022 Page 17 of 17 240V MODELS 208V MODELS...

Page 18: ...drain For commercial use we recommend checking with your local inspectors to confirm the steamer system is acceptable for your use Many jurisdictions will require an ASME boiler for commercial use WA...

Page 19: ...ION continued IMPORTANT Before deciding on a mounting location please read through these installation instructions completely and take a careful look at al of the diagrams An exhaust fan installed out...

Page 20: ...YPICAL DRAIN LINES DIAGRAM 5 TYPICAL STEAM LINES IMPORTANT Input water pressure must be 20 100 psi 138 689 kPa If the generators are mounted in a place difficult for the home owner to access the water...

Page 21: ...instructions document 4211 1661 for details regarding plumbing of the individual steamers in your system INSTALL THE PRESSURE RELIEF VALVE Each steamer must have its own pressure safety valve 10psi 69...

Page 22: ...Refer to the wiring diagrams to determine your connection points and the necessary jumper connection Connections can be varied to use either single phase or 3 phase or 3 phase Neutral Connect the eart...

Page 23: ...s the ON OFF switch 6 Within one minute the units should again produce steam The generators should call for water once every two minutes or more depending on their power rating It s normal for the flo...

Page 24: ...TERIORCONTROLISMOUNTEDOUTSIDETHEENCLOSURETO ALLOW FOR EASY ADJUSTMENTS TO THE TIME AND TEMPERATURE STEAMBATH SCHEDULE THE INTERIOR CONTROLIS MOUNTED INSIDE THE ENCLOSURE TO ALLOW TEMPERATURE SENSING A...

Page 25: ...Description Page Important Safety Instructions 3 1A Exterior Control Overview 4 1B Interior Control Overview 4 2 Operation of Your WWSUP18 and WWSUP19 Controls 4 3 How toTake a Steambath 4 4 Maintena...

Page 26: ...hould consult a physician regarding correct exposure e Obese persons and persons with a history of heart disease low or high blood pressure circulatory system problems or diabetes should consult a phy...

Page 27: ...The control will alternately display time remaining and the actual temperature at the sensor in your steam room every 5 seconds 4 To change the time setting press and hold the TIME button on the cont...

Page 28: ...emperature adjustment needs setting 1 See Section 3 Temperature Adjustment 2 Call WATERWORKS Service Department Control ON exterior or interior Control displays E001 Temperature sensor not connected 1...

Page 29: ...4209 55 REV A 01 28 2022 WWSU46 OWNERS MANUAL page 6...

Reviews: