Selecting the Concentrate Source—F5
1. Enter the calibration/setup mode. Refer to:
"Entering the Calibration/Setup Mode" on page 60
.
2. Navigate to
(F5 parameter).
3. Press the
(SELECT button) to edit the parameter.
4. Use the
or
(up or down button) to display the desired
foam tank pairing:
• Select
(AA) when you source from a single tank that
supplies A foam or when you source from 2 tanks that supply A
foam. The proportioning value for this setting is between 0.1% to
1.0% for both tanks.
• Select
(Ab) when you source from 2 tanks that supply
A foam from one tank (tank A) and B foam from the other tank (tank
B). The proportioning value for this setting is between 0.1% to 1.0%
for the A foam tank and 1.0%, 3.0% and, 6.0% from the B foam
tank.
• Select
(bb) when you source from a single tank that
supplies B foam or when you source from 2 tanks that supply B
foam. The proportioning value for this setting is 1.0%, 3.0% or,
6.0% for both tanks.
• Select
(AF) when you source from a 2 tanks that
supply combination A/B foam. The proportioning value for this
setting is between 0.1% to 1.0%, 3.0% or, 6.0% for both tanks.
5. Press the
(SELECT button) to return to the
(F5
parameter).
6. Press the
(FOAM button) to save the value and exit the
calibration and
s
etup mode.
Simulating Water Flow—F6
Use this mode to test and verify the foam system operation. This
function is available for the AQUIS 1.5 with digital head, AQUIS 3.0 and
AQUIS 6.0.
1. Enter the calibration/setup mode. Refer to:
"Entering the Calibration/Setup Mode" on page 60
.
2. Navigate to
(F6 parameter).
3. Press the
(SELECT button) to edit the parameter.
4. Use the
or
(up or down button) to display the desired
simulated flow rate from the following choices:
Flow Rate Settings
AQUIS 1.5
0
50
100
200
AQUIS 3.0
0
50
100
200
AQUIS 6.0
0
100
200
300
5. Press the
(SELECT button) to save the value.
6. Position the inject/bypass valve to bypass. Refer to:
"Operating the Inject/Bypass Valve" on page 71
.
7. Press the
(FOAM button) to start the pump.
Note:
Make sure that the output has equalized for up to 3 minutes before
you collect the concentrate.
8.
Collect the concentrate that flows from the bypass hose for 1 minute.
9. Press the
(FOAM button) to stop the pump.
10. Measure the volume of concentrate.