Calibrating—Manual OIT
1. Rotate the
(FOAM % dial) to 0.
2. Press and hold the
(ON/OFF button) for 6 seconds.
3.
Establish a water flow of 50 gallons per minute.
4. Press the
(ON/OFF button), the LEDs flash as follows:
• The
(blue LED) flashes 3 times to indicate that the pump is
calibrated.
• The
(red LED) flashes continuously if there was an error during
the calibration process. The value was not changed.
Default mix percentage
0.1% 0.2% 0.3% 0.4% .05% 0.6% 0.7% 0.8% 0.9% 1.0%
Fl
ow r
at
e
U
S g
al
lon
s
100
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
200
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
300
0.3
0.6 0.9
1.2
1.5
1.8
2.1
2.4
2.7
3.0
Note:
Refer to NFPA guidelines for flow testing.
Calibrating and Setup—Digital OIT
Entering the Calibration/Setup Mode
1. Press and hold the
(SELECT button).
2. After 5 seconds, the
(5 second value) is displayed.
3. Continue holding the
(SELECT button) and then press the
(up and down buttons) simultaneously.
4. The
(calibration value) is displayed, then after 2
seconds the
(function value) displays.
5. Press the
or
(up or down button) to navigate to the
desired parameter.
6. Press the
(FOAM button) to save the value and exit the
calibration and
s
etup mode.