Calibrating the Flow Rate—F3
Note:
Ensure that you selected the desired units of measure before you
perform this calibration.
1. Use your preferred method of measurement to determine the actual
flow rate of water at the flowmeter. Remember this value.
2. Enter the calibration/setup mode. Refer to:
"Entering the Calibration/Setup Mode" on page 60
.
3. Navigate to
(F3 parameter).
4. Press the
(SELECT button) to enter the parameter.
5.
The display shows the value that the flowmeter is measuring.
• If the value that you measured and the displayed value match,
press the
(FOAM button) to save the value and exit the
calibration and
s
etup mode.
• If the value that you measured and the displayed value do not
match, press
or
(up or down button) to adjust the
display value to match the value that you measured.
• When the
(low flow) value is displayed, an insufficient
amount of water is flowing though the flowmeter.
6. Press the
(SELECT button) to return to the
(F3
parameter).
7. Press the
(FOAM button) to save the value and exit the
calibration and
s
etup mode.
Enabling System Lockout—F4
Note:
Use the menu lockout to prevent unintentional changes to a
parameter.
1. Enter the calibration/setup mode. Refer to:
"Entering the Calibration/Setup Mode" on page 60
.
2. Navigate to
(F4 parameter).
3. Press the
(select button) to edit the parameter. The
(enable setting) is displayed.
4. Use the
(up button) to display the
(lock setting).
5. Press the
(SELECT button) to return to the
(F4
parameter).
6. Press the
(FOAM button) to save the value and exit the
calibration and
s
etup mode.
Note:
Contact Waterous for more information about locking and
unlocking the OIT.