Page 34
WS2H, WS2HF, and WS3 Manual
Modbus
Register
Description
Valid
Values
Properties
40001
Year
0-99
R/W
40002
Month
1-12
R./W
40003
Day
1-31
R/W
40004
Day of Week
0-6
R/W
40005
Hour (24 Hour Format)
0-23
R/W
40006
Minute
0-59
R/W
40007
Seconds
0-59
R/W
40008
Days left until next regeneration
R
40009
System fl ow rate x 10 (GPM or LPM)
R
40010
System Total High Word (GAL or L)
R
40011
System Total Low Word (GAL or L)
R
40012
Regen Unit
1-16
R/W
40013
Valve 1 Flow Rate
R
40014
Valve 1 Capacity Remaining High Word (GAL or L)
R
40015
Valve 1 Capacity Remaining Low Word (GAL or L)
R
40016
Valve 1 Total Usage High Word (GAL or L)
R
40017
Valve 1 Total Usage Low Word (GAL or L)
R
40018
Valve 1 Flags High Word (GAL or L)
R
40019
Valve 1 Flags Low Word (GAL or L)
R
40020
Valve 1 Error Value
R
Registers for Valves 2 through 15 contain the same information as Valve
1 and repeat. For example, register 40021 is Valve 2 Flow Rate, register
40029 is Valve 3 Flow Rate and so on.
40133
Valve 16 Flow Rate
R
40134
Valve 16 Capacity Remaining High Word (GAL or L)
R
40135
Valve 16 Capacity Remaining Low Word (GAL or L)
R
40136
Valve 16 Total Usage High Word (GAL or L)
R
40137
Valve 16 Total Usage Low Word (GAL or L)
R
40138
Valve 16 Flags High Word (GAL or L)
R
40139
Valve 16 Flags Low Word (GAL or L)
R
40140
Valve 16 Error Value
R
40141
Next Regen Unit (upper byte) and Days Remaining (lower byte)
R
40142
Valve 1 Status
0-Not Connected
1-Service
2-Service Fill
3-Regen Fill
4-Regen
5-Regen Rinse
6-Error
7-Standby
R
40143
Valve 2 Status
R
40144
Valve 3 Status
R
40145
Valve 4 Status
R
40146
Valve 5 Status
R
40147
Valve 6 Status
R
40148
Valve 7 Status
R
40149
Valve 8 Status
R
40150
Valve 9 Status
R
40151
Valve 10 Status
R
40152
Valve 11 Status
R
40153
Valve 12 Status
R
40154
Valve 13 Status
R
40155
Valve 14 Status
R
40156
Valve 15 Status
R
40157
Valve 16 Status
R
MODBUS INFORMATION (CONTINUED)