Page 32
WS2H, WS2HF, and WS3 Manual
CUSTOM MOTORIZED DRIVE TIMING
• Used to alter the standard timing sequence of the motorized isolation valve for
complete custom timing of the drive circuits
- Setup procedure applies to both the “Bypass” drive and “Aux” drive
• Customization needs to be done after defi ning the regeneration cycle sequence
• Accessed by pressing the UP and DOWN arrows simultaneously while in the No
Hard Water Bypass selection
- Next will scroll through each cycle of the regeneration program
- Arrow buttons toggle Standby and Online indicating the desired position the
drive during that cycle of the regeneration.
- In the example screens the “Bypass” drive will be transitioning offl ine for
Backwash (Cycle 1) and coming online for Fill (Cycle 5).
• Timing can be further customized per cycle by adding a time delay to the
sequence
- Accessed by pressing the UP and DOWN arrows simultaneously while in the
drive sequence screens
- Setting a “Start Time” delays the start of that transition after reaching set cycle
- A second time screen then sets the time the drive maintains that set position
before transition back to its previous position.
- “Regen” will be illuminated to identify that a sequence has a time modifi er
associated with it
- In the example screens the “Bypass” drive will delay its transition to offl ine until 2
minutes into Backwash (Cycle 1) and coming online for Fill (Cycle 5).
RETURN TO NORMAL
OPERATION
RETURN TO NORMAL
OPERATION
SET BYPASS CONTROL
HARD WATER BYPASS
NO HARD WATER BYPASS
SEPARATE SOURCE INLET
SIMPLE ALT SHARING MAV
RELAY