WS2H, WS2HF, and WS3 Manual
Page
47
Drawing No.
Order No.
Description
Quantity
2H
2HF
3”
V3003-02
See Meter Instructions
1
V3118-03
WS1.5/2H Meter Commercial Asy
1
2
V3632
Commercial Meter Retaining Clip
1
3
V3118-03
Turbine Asy
1
4
V3501
Commercial Meter Turbine Clip
1
5
V3105
O-ring - 215
1
INLINE FLOW METER ASSEMBLY
Typical meter retaining clip
installation. Ensure clip is fully
engaged in groove and tabs
positioned in slot as shown.
Service or replace the turbine by:
1. Turn the bypass for the system off and relieve the pressure on the system.
2. Press downward on the remote meter assembly to relieve tension on the retaining clip V3632 (or the U-shaped
V3223 WS2 Meter Clip). Remove the clip and take the meter assembly out of the housing.
3. Remove the bend from the two exposed tips of the retaining clip V3501 and remove clip.
4. Service or replace the V3118-03 WS15/2 Turbine Assembly and place it back in the turbine shaft.
5. Insert the V3501 WS15/2 Turbine Clip and re-bend the exposed ends of the clip. The V3118-03 turbine has a
groove to line up with the V3501 WS15/2 Turbine Clip.
6. Insert meter assembly back into the meter housing.
7. Re-install the meter retaining clip V3632 as shown below (or the U-shaped V3223 WS2 Meter Clip).
8. Open the bypass for the system slowly to bring back into service and check to be sure you have no water leaks.