2
2.2 Electrical
Inputs
Input power
100 – 120/220-240 VAC ±10%, 12A, 50/60 Hz
Fuse
1.6A, 5 x 20mm
Input signals
State-Type Digital Inputs
Electrical: Non-isolated 5 VDC with 301K ohm pull-up
Typical response time: <10 seconds
Devices supported: Any isolated dry contact (i.e. relay, reed switch)
Types: Interlock, Level switch, Generic input
Low Speed Counter-Type
Digial Inputs
Electrical: Non-isolated 5 VDC with 301K ohm pull-up, 0-10 Hz, 50 msec minimum
width
Devices supported: Any device with isolated open drain, open collector, transistor or
reed switch
Supported on inputs: Standard inputs A-D, Optional inputs 1-6
Types: Contacting Flowmeter, Feed Verification, Generic Counter
High Speed Counter-Type
Digial Inputs
Electrical: Non-isolated 5 VDC with 301K ohm pull-up, 0-400 Hz, 1.25 msec
minimum width
Devices supported: Any device with isolated open drain, open collector, transistor or
reed switch
Supported on inputs: Standard inputs A-D, Optional inputs 5-6
Types: Paddlewheel Flowmeter, Generic Counter
Analog Inputs (1-8)
(Optional)
4-20 mA, 2-wire or 3 -wire, internally powered by 24 VDC, 25 ohm input resistance,
1000 ohm maximum load. Typical response time <10 seconds
Sensor STANDARD
(1)
Sensor OPTIONAL (3)
Signal (isolated)
±1.5V
Signal
(isolated)
±1.5V
Temp (isolated)
1K or 10K or 100K ohm
Temp (isolated)
1K or 10K or 100K ohm
Outputs
STANDARD
Mechanical relays:
At 115 VAC, 10 amp (resistive), 1/8 HP
At 230 VAC, 6 amp (resistive), 1/8 HP
R1, R2, R3, and R4 relays are fused together as one group, total current for this group must not exceed 5.5A
R5, R6, R7 and R8 relays are fused together as one group, total current for this group must not exceed 5.5A.
Relays 1-8 may be dry contact or may switch line (mains) voltage, depending upon model code; refer to Figure 4. Powered
relays have both NO and NC terminals available. Only powered relays are fused.
Digital:
USB
Ethernet, 10 Base T
OPTIONAL
4-20 mA (1-4):
Isolated, 500 ohm max. resistive load, internally powered
Agency Approvals
Safety
ANSI/UL 61010-1:2012 3rd Ed.
C22.2 No. 61010-1:2012 3rd Ed.
IEC 61010-1:2010 3rd Ed.
EN 61010-1:2010 3rd Ed.
EMC IEC
61326-1:2005
EN
61326-1:2006
Note: For EN61000-4-6, and EN 61000-4-3, the controller meets performance criteria B.
*Class A equipment: Equipment suitable for use in establishments other than domestic, and those directly connected
to a low voltage (100-240 VAC) power supply network which supplies buildings used for domestic purposes.