216 • I/O modules
Analog Outputs 750-552, -554, (-584)
Modular I/O System
ETHERNET TCP/IP
For fieldbus masters with the ability to evaluate the status information within
the data word, i.e. Siemens format.
The status information is contained in Bit B2 .. B0.
The digitized input is placed at the position Bit B3 .. B15.
750-552/000-200
Output current
0-20 mA
Value
Binary
Hex.
Dec.
20
0100 0000 0000 0000
40 00
16384
17.5
0011 1000 0000 0000
38 00
14336
15
0011 0000 0000 0000
30 00
12288
12.5
0010 1000 0000 0000
28 00
10240
10
0010 0000 0000 0000
20 00
8192
7.5
0001 1000 0000 0000
18 00
6144
5
0001 0000 0000 0000
10 00
4096
2.5
0000 1000 0000 0000
08 00
2048
0
0000 0000 0000 0000
00 00
0
750-554/000-200
Output current
4-20 mA
Value
Binary
Hex.
Dec.
20
0100 0000 0000 0000
40 00
16384
16
0011 0000 0000 0000
30 00
12288
12
0010 0000 0000 0000
20 00
8192
8
0001 0000 0000 0000
10 00
4096
4.015
0000 0000 0001 0000
0010
16
4
0000 0000 0000 0000
0000
0