140 • I/O modules
Digital Outputs 750-507
Modular I/O System
ETHERNET TCP/IP
Technical Data:
Item-No.:
507
Number of outputs
2
Input current (internal)
15 mA
Voltage via power jumper contacts
DC 24 V (- 15 % / + 20 %)
Kind of load
resistive, inductive, lamps
Reverse voltage protection
yes
Output current
2.0 A short-circuit protected
Short circuit limitation
I
(scp)
42 A typ.
I
(scr)
33 A typ.
Open circuit detection
I
I(off)
< 30
µ
A typ.
GrenzFrequency
2.5 kHz
Diagnostics
Open-circuit, Overload and short circuit
Isolation
500 V System/power supply
Input current (field side)
15 mA typ. + load
Internal bit width
2 in; 2 out
Configuration
without address or configuration adjustment
Operating temperature
0 °C ... + 55 °C
Wire connection
CAGE CLAMP
; 0.08 mm
2
- 2.5 mm
2
, AWG 28 – 14,
8 – 9 mm Stripped length
Dimensions (mm) WxHxL
12 x 64* x 100 (*from upper edge of carrier rail)
The possibility for diagnostics with 750-507 with each output channel:
Status from PLC to
module
LED green
(Output)
LED red
(diagnostic)
Description
H
ON
OFF
L
OFF
OFF
Output O.K.
H
ON
OFF
L
OFF
ON
OPEN circuit*
)
H
OFF
ON
L
OFF
OFF
Short circuit with GND*
)
H
ON
OFF
L
ON
ON
Short circuit with +24 V. *
)
H
OFF
ON
L
OFF
ON
Overtemperature or
Over- or Undervoltage *
)
*
)