160 • I/O modules
Digital Outputs 750-517
Modular I/O System
ETHERNET TCP/IP
4.3.1.1.11 Digital Output Relay
(2 changeover contacts isolated outputs, AC 250 V, 1 A)
750-517
14 24
K1 K2
C
D
B
A
11 21
12 22
750-517
Data contacts
Relay 2
Status
Relay 1
Status
DO 2
L 2
DO 2
DO 1
L 1
DO 1
DO 2
N
N
Technical description
The power supply for the relay coils is not made via the power jumper contacts
but directly from the electronics. The respective output contacts of the swit-
ching element are therefore always positioned at the field side.
The power supply is made via a series-connected supply terminal block for the
respective operating voltage. Power connections are made automatically from
module to module when snapped onto the DIN rail. One termination point of
these contacts must be directly connected to the power supply.
These I/O modules are not provided with integrated power jumper contacts.
Care should be taken to supply each isolated module with separate power
supply connections.
The output module can operate with all buscouplers of the
WAGO-I/O-SYSTEM.