I/O modules • 195
Analog Inputs 750-468, (-488)
Modular I/O System
ETHERNET TCP/IP
Numerical format for Siemens function blocks
For fieldbus masters with the ability to evaluate the status information within
the data word, i.e. Siemens format.
The status information is contained in Bit B0 .. B2.
The digitized input is placed at the position Bit B3 .. B15.
750-468/000-200 (formerly 750-488)
Input
voltage
0-10V
Value
Binary
X E O*)
Hex.
Dec.
Status
>10
0101 0000 0000 0000
0 0 1
50 01
20481
42
10
0101 0000 0000 0000
0 0 0
50 00
20480
0
5
0011 0000 0000 0000
0 0 0
30 00
12288
0
2.5
0010 0000 0000 0000
0 0 0
20 00
8192
0
1.25
0001 1000 0000 0000
0 0 0
18 00
6144
0
0.0049
0001 0000 0000 1000
0 0 0
10 08
4104
0
0
0001 0000 0000 0000
0 0 0
10 00
4096
0
*)
X : without meaning, E : short circuit or open circuit, O : overflow