I/O modules • 215
Analog Outputs 750-552, -554, (-584)
Modular I/O System
ETHERNET TCP/IP
Technical Data:
Item-No.:
750-552,
750-552/000-200*
)
750-554,
750-554/000-200*
)
(formerly 750-584)
Number of outputs
2
Input current (internal)
60 mA max.
Nominal voltage
DC 24 V (-15% / +20%) via power jumper contacts
Signal current
0-20 mA
4-20 mA
Resistance
< 500
Ω
Linearity
±
2 LSB (last Significant Bit)
Resolution
12 Bit
(*
)
12 Bit + sign for the variations
750-552/000-200 and 750-554/000-200)
Isolation
500V System/power supply
Bit width per channel
16Bit: Data
Configuration
none, or via software with the consent of WAGO
Operating temperature
0°C....+55°C
Wire connection
CAGE CLAMP
; 0.08 mm
2
- 2.5 mm
2
, AWG 28 – 14,
8 – 9 mm Stripped length
Dimensions (mm) WxHxL
12 x 64* x 100 (*from upper edge of carrier rail)
Numerical format
All analog values will be shown in a numerical format. The following table
will explain the numerical format
.
(750-552/554). The 3 LSBs are not signifi-
cant.
750-552, 750-554
Output current
0-20 mA
Output current
4-20 mA
Value
Binary
Hex.
Dec.
20
20
0111 1111 1111 1111
7F FF
32767
10
12
0100 0000 0000 0000
40 00
16384
5
8
0010 0000 0000 0000
20 00
8192
2.5
6
0001 0000 0000 0000
10 00
4096
0.156
4.125
0000 0001 0000 0000
01 00
256
0.01
4.0078
0000 0000 0001 0000
00 10
16
0.005
4.0039
0000 0000 0000 1000
00 08
8
0
4
0000 0000 0000 0111
00 07
7
0
4
0000 0000 0000 0000
0
0
Numerical format for Siemens function blocks