WAGO-I/O-SYSTEM 750
I/O Modules 119
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
10.2.4 Type 2 - Up Counter
Occupied input process image [(channel x) bits]:
(1x) 48
Occupied output process image [(channel x) bits]: (1x) 48
Items that use this mapping type:
0750-0404, 0750-0404/0000-0001
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Status clock
I
0
1
BOOL
Status up/down
I
0
2
BOOL
Status out 1
I
0
3
BOOL
Status out 2
I
0
4
BOOL
Status block counter
I
0
5
BOOL
Status set counter
I
2
WORD
Actual count value Low Word
I
4
WORD
Actual count value High Word
Q
0
2
BOOL
Control out 1
Q
0
3
BOOL
Control out 2
Q
0
4
BOOL
Control block counter
Q
0
5
BOOL
Control set counter
Q
2
WORD
Set value Low Word
Q
4
WORD
Set value High Word
10.2.5 Type 3 - Peak Time Counter type 1
Occupied input process image [(channel x) bits]:
(1x) 48
Occupied output process image [(channel x) bits]: (1x) 48
Items that use this mapping type:
0750-0404/0000-0002
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BOOL
Toggle bit
I
0
1
BOOL
Status up/down
I
0
2
BOOL
Status out 1
I
0
3
BOOL
Status out 2
I
0
5
BOOL
Confirmation start count pulse acquisition
I
2
WORD
Actual count value Low Word
I
4
WORD
Actual count value High Word
Q
0
2
BOOL
Control out 1
Q
0
3
BOOL
Control out 2
Q
0
5
BOOL
Control bit start count pulse acquisition
Q
2
WORD
Set value Low Word
Q
4
WORD
Set value High Word