158 I/O Modules
WAGO-I/O-SYSTEM 750
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
10.2.59 Type 60 - Proportional Valve Module 6 Bytes
Occupied input process image [(channel x) bits]:
(1x) 48
Occupied output process image [(channel x) bits]: (1x) 48
Items that use this mapping type:
0750-0632#6, 0750-0632/0000-0100#6
Data mapping:
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BYTE
KBUS_ST
I
1
0
BYTE
MBX_ST
I
2
0
BYTE
MBX_Input_Data_1
I
3
0
BOOL
V1_READY
I
3
1
BOOL
V1_ON_TARGET
I
3
3
BOOL
V1_DI2
I
3
4
BOOL
V1_DI1
I
3
5
BOOL
V1_DITHER_ST
I
3
6
BOOL
V1_JOGNEG_ACK
I
3
7
BOOL
V1_JOGPOS_ACK
I
4
0
INT
V1_COIL_CURRENT_IN
Q
0
0
BYTE
KBUS_CTRL
Q
1
0
BYTE
MBX_CTRL
Q
2
0
BYTE
MBX_Output_Data_1
Q
3
0
BOOL
V1_PWR_EN
Q
3
1
BOOL
V1_SPL_EN
Q
3
3
BOOL
V1_RSEL_0
Q
3
4
BOOL
V1_RSEL_1
Q
3
5
BOOL
V1_DITHER_CTRL
Q
3
6
BOOL
V1_JOGNEG
Q
3
7
BOOL
V1_JOGPOS
Q
4
0
INT
V1_COIL_CURRENT_OUT