WAGO-I/O-SYSTEM 750
I/O Modules 159
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
10.2.60 Type 61 - Proportional Valve Module 12 Bytes
Occupied input process image [(channel x) bits]:
(1x) 96
Occupied output process image [(channel x) bits]: (1x) 96
Items that use this mapping type:
0750-0632#12, 0750-0632/0000-0100#12
Data mapping (for symmetrical channels, only the first channel is specified):
I/Q
Byte
Bit
Data Type
Contents
I
0
0
BYTE
KBUS_ST
I
1
0
BYTE
MBX_ST
I
2
0
BYTE
MBX_Input_Data_1
I
3
0
BYTE
MBX_Input_Data_2
I
4
0
BYTE
MBX_Input_Data_3
I
5
0
BYTE
MBX_Input_Data_4
I
6
0
BOOL
V1_READY
I
6
1
BOOL
V1_ON_TARGET
I
6
3
BOOL
V1_DI2
I
6
4
BOOL
V1_DI1
I
6
5
BOOL
V1_DITHER_ST
I
6
6
BOOL
V1_JOGNEG_ACK
I
6
7
BOOL
V1_JOGPOS_ACK
I
7
0
BOOL
V2_READY
I
7
1
BOOL
V2_ON_TARGET
I
7
5
BOOL
V2_DITHER_ST
I
7
6
BOOL
V2_JOGNEG_ACK
I
7
7
BOOL
V2_JOGPOS_ACK
I
8
0
INT
V1_COIL_CURRENT_IN
I
10
0
INT
V2_COIL_CURRENT_IN
Q
0
0
BYTE
KBUS_CTRL
Q
1
0
BYTE
MBX_CTRL
Q
2
0
BYTE
MBX_Output_Data_1
Q
3
0
BYTE
MBX_Output_Data_2
Q
4
0
BYTE
MBX_Output_Data_3
Q
5
0
BYTE
MBX_Output_Data_4
Q
6
0
BOOL
V1_PWR_EN
Q
6
1
BOOL
V1_SPL_EN
Q
6
3
BOOL
V1_RSEL_0
Q
6
4
BOOL
V1_RSEL_1
Q
6
5
BOOL
V1_DITHER_CTRL
Q
6
6
BOOL
V1_JOGNEG
Q
6
7
BOOL
V1_JOGPOS
Q
7
0
BOOL
V2_PWR_EN
Q
7
1
BOOL
V2_SPL_EN
Q
7
3
BOOL
V2_RSEL_0
Q
7
4
BOOL
V2_RSEL_1
Q
7
5
BOOL
V2_DITHER_CTRL
Q
7
6
BOOL
V2_JOGNEG
Q
7
7
BOOL
V2_JOGPOS
Q
8
0
INT
V1_COIL_CURRENT_OUT
Q
10
0
INT
V2_COIL_CURRENT_OUT