WAGO-I/O-SYSTEM 750
Commissioning 95
750-325 CC-Link Fieldbus Coupler
Manual
Version 2.0.1
8.6
Restoring Factory Settings
To restore the factory settings, proceed as follows:
1.
Switch off the supply voltage of the fieldbus controller.
2.
Reset the DIP switch of the fieldbus coupler to the factory settings as
follows:
Pin
Value
Function
8
1
CC-Link V2.0
6/7
0/1
4 cycles
4/5
1/1
4 occupied stations
1/2/3
0/0/1
10 MBaud
3.
Switch on the supply voltage of the fieldbus controller.
A restart of the fieldbus node is implemented automatically.
The start takes place with the default settings.