The areas shown in the following table are allocated for the digital data (remote
I/O) depending on the number of occupied stations and depending on the
selected cycles of the extended cyclic setting assigned from the master station.
In this table "RX" stands for the input bits and "RY" for the output bits, which are
specified bit by bit with "points".
"RWw" is the readable register words, and "RWw" is the changeable register
words, which are indicated by words with "words".
Table 31: Assigned Areas depending in the CC-Link Configuration Setting
Number of
occupied
s
tations
CC-Link Version
Version 1.1
Version 2.0
-
1 Cycle 2 Cycles
4 Cycles
8 Cycles
1
RX, RY
each
32 points
each
32 points
each
64 points
each
128 points
RWr, RWw
4 words
each
8 words
each
16 words
each
32 words
2
RX, RY
each
64 points
each
96 points
each
192 points
each
384 points
RWr, RWw
8 words
each
16 words
each
32 words
each
64 words
3
RX, RY
each
96 points
each
160 points
each
320 points
each
640 points
RWr, RWw
12 words
each
24 words
each
48 words
each
96 words
4
RX, RY
each
128 points
each
224 points
each
448 points
each
896 points
RWr, RWw
16 words
each
32 words
each
64 words
each
128 words
16 Points for System!