Technical Data
G50 /G 70/G 85
88
6.2
Generator Data
Item Number:
G 50
0009366
0009467
0620001
G 70
0009367
0009468
0620002
G 70
0620350
0620351
0620352
G 85
0009369
0009459
0620003
Generator
Make/Type
Mecc Alte / Brushless
Model
ECO32-3S/4
ECO32-2L/4
ECO32-3L/4
ECO32-3L/4
Generator speed
rpm
1800
Voltage selector
switch
3 position
AC voltages
available
120/240 zig-zag
120/208 low-wye
277/480 Hi-wye
Frequency
60 Hz
Power factor
1ø
3ø
1.0
0.8
Voltage regulation
±1.00%
Insulation class
H
Sound level at 7 m
(23 ft.)
dB(A)
66
68
69
AC receptacles
2 duplex, 3 twist-lock
1ø 120 GFI duplex
Amps
2-20
1ø 120/240 V twist
lock
Amps
1-30A 2-50A
Standby Output
kW/
kVA
42/53
63/79
74/92
Continuous Output
kW/
kVA
38/48
58/72
67/84
Main breaker
Amps
175
225
250
Summary of Contents for G70
Page 2: ......
Page 14: ...Safety Information G 50 G 70 G 85 wc_si000158gb fm 14 2 6 Label Location...
Page 15: ...G 50 G 70 G 85 Safety Information wc_si000158gb fm 15...
Page 24: ...Operation G 50 G 70 G 85 wc_tx000483gb fm 24 3 Operation 3 1 Control Panels...
Page 46: ...Operation G 50 G 70 G 85 wc_tx000483gb fm 46 w c _ g r 0 0 0 5 1 0 a d c b...
Page 57: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 57...
Page 59: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 59...
Page 65: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 65 G 50 G 70 Engine Wiring...
Page 67: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 67 G 50 G 70 Engine Wiring...
Page 69: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 69 G 50 G 70 Engine Wiring...
Page 73: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 73...
Page 81: ...Mobile Generators Factory Installed Options wc_tx000380gb fm 81 Notes...
Page 90: ...Technical Data G50 G 70 G 85 90 6 4 Dimensions mm inches...
Page 91: ......