3.28 Automatic/Remote Start-up
See Graphic: wc_gr002611
In the “REMOTE START” position the generator can be started
remotely, either through a transfer switch or some other type of remote
start switch. “REMOTE START” is the normal setting when using the
generator as a standby power supply. Before placing the generator in
the automatic start-up mode, review the pre-start and manual Start-up
sections in this manual and follow procedure below.
Before placing the Engine Start Switch (f) in the “REMOTE
START” position,
verify that the contacts on any remote switch linked
to the generator set are OPEN. This will prevent the generator from
immediately starting when the Engine Start Switch is moved to the
“REMOTE START” position.
3.28.1
Perform a manual start at least once to verify that the metering panel
is operating correctly. Refer to Section
Before Starting
and
Manual
Start-up
sections in this manual.
3.28.2
If a check of auto start-up circuit is desired, attach a short jumper wire
(minimum 16 gauge insulated) between the two terminals on the
remote run terminal block. This applies a ground to the Engine Control
Module to complete the start circuit. The engine should crank, start and
run.
Move the Engine Start Switch to off “O” to stop engine. Remove jumper
from remote run terminals after testing is complete.
3.28.3
Secure generator by closing and locking all doors.
3.28.4
Set Engine Start Switch to “REMOTE START” and close main line
circuit breaker.
The generator is now ready for automatic start-up.
If the generator is to be used as a stand-by power supply for more than
a month, provisions must be made to maintain battery charge. This can
be done either by attaching a battery charger to the battery or by
starting generator manually and running engine periodically to
maintain charge. See Section
Manual Start-up
.
WARNING
Summary of Contents for G70
Page 2: ......
Page 14: ...Safety Information G 50 G 70 G 85 wc_si000158gb fm 14 2 6 Label Location...
Page 15: ...G 50 G 70 G 85 Safety Information wc_si000158gb fm 15...
Page 24: ...Operation G 50 G 70 G 85 wc_tx000483gb fm 24 3 Operation 3 1 Control Panels...
Page 46: ...Operation G 50 G 70 G 85 wc_tx000483gb fm 46 w c _ g r 0 0 0 5 1 0 a d c b...
Page 57: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 57...
Page 59: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 59...
Page 65: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 65 G 50 G 70 Engine Wiring...
Page 67: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 67 G 50 G 70 Engine Wiring...
Page 69: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 69 G 50 G 70 Engine Wiring...
Page 73: ...G 50 G 70 G 85 Maintenance wc_tx000484gb fm 73...
Page 81: ...Mobile Generators Factory Installed Options wc_tx000380gb fm 81 Notes...
Page 90: ...Technical Data G50 G 70 G 85 90 6 4 Dimensions mm inches...
Page 91: ......