Operating the Machine
50Hz Mobile Generators
wc_tx000884gb.fm
28
3.9
Stopping the Generator
Prerequisites
All tools disconnected from generator
Wheels of trailer chocked
Procedure
Follow the procedure below to stop the generator.
1. Disconnect all tools from the generator.
2. Place the main circuit breaker and the individual circuit breakers in the OFF
position.
3. Allow the engine to run 2–3 minutes to cool down.
4. Press the STOP push button.
5. Turn the ENGINE PROTECTION switch to the OFF position (0).
6. Place the control switch in the LOCKED ENGINE position.
7. Place the battery cut-off switch
(l)
in the OFF position.
If storing the machine, see section
Transporting, Lifting, and Storing
.
CR
CG
ENTER