3.8
Starting the Generator
Prerequisites
Machine on a flat, horizontal surface
Wheels of trailer chocked
Procedure
Follow the procedure below to start the generator.
1. Disconnect all loads from the generator.
2. Place the battery cut-off switch
(n)
in the ON position.
3. Place the fuel valves
(o)
in the appropriate OPEN position.
4. Place the control switch in the MANUAL START position.
5. Turn the ENGINE PROTECTION switch to the ON position (1).
6. Press the START push button. Release the START push button when the
engine starts.
NOTICE:
Do not hold the START push button depressed for more than 20 sec-
onds. Damage to the starter may occur. Allow 30 second of cooling time between
starting attempts.
CR
CG
ENTER
Summary of Contents for G 43
Page 1: ...Mobile Generator G 43 OPERATOR S MANUAL 0175257en 001 0608 0 1 7 5 2 5 7 E N...
Page 2: ......
Page 4: ...Foreword G 43 wc_tx000898gb fm 4...
Page 13: ...50Hz Mobile Generators Safety Information wc_si000271gb fm 13 Notes...
Page 18: ...Transporting Lifting and Storing 50Hz Mobile Generators wc_tx000895gb fm 18 Notes...
Page 48: ...Schematics 50Hz Mobile Generators wc_tx000886gb fm 48 5 Schematics 5 1 Power Wiring...
Page 50: ...Schematics 50Hz Mobile Generators wc_tx000886gb fm 50 5 3 Engine Wiring...
Page 52: ...Schematics 50Hz Mobile Generators wc_tx000886gb fm 52 5 5 Socket Wiring...
Page 54: ...Schematics 50Hz Mobile Generators wc_tx000886gb fm 54 5 7 Control Wiring...
Page 57: ...50Hz Mobile Generators Basic Troubleshooting wc_tx000896gb fm 57...
Page 60: ...Technical Data G 43 wc_td000277gb fm 60 7 3 Dimensions...
Page 62: ......
Page 64: ......